225 Amp Cable Size at 150 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 1.2V (2.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.96V (12.41%)
Voltage at Load46.8 VLine Loss: 270.8 W
Max Power & Breaker10.8 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A963.0 V (2006.25%)0.0 V1588.5 V (3309.38%)216675.0 WDrop High
2.5 mm²24 A18 A577.8 V (1203.75%)0.0 V953.1 V (1985.62%)130005.0 WDrop High
4 mm²32 A25 A361.12 V (752.34%)0.0 V595.69 V (1241.02%)81253.1 WDrop High
6 mm²41 A32 A240.75 V (501.56%)0.0 V397.12 V (827.34%)54168.8 WDrop High
10 mm²57 A44 A144.45 V (300.94%)0.0 V238.27 V (496.41%)32501.2 WDrop High
16 mm²76 A59 A90.28 V (188.09%)0.0 V148.92 V (310.25%)20313.3 WDrop High
25 mm²101 A78 A57.78 V (120.37%)0.0 V95.31 V (198.56%)13000.5 WDrop High
35 mm²125 A97 A41.27 V (85.98%)6.7 V68.08 V (141.83%)9286.1 WDrop High
50 mm²151 A118 A28.89 V (60.19%)19.1 V47.65 V (99.28%)6500.2 WDrop High
70 mm²192 A150 A20.64 V (42.99%)27.4 V34.04 V (70.92%)4643.0 WDrop High
95 mm²232 A181 A15.21 V (31.68%)32.8 V25.08 V (52.25%)3421.2 WDrop High
120 mm²269 A210 A12.04 V (25.08%)36.0 V19.86 V (41.37%)2708.4 WDrop High
150 mm²309 A241 A9.63 V (20.06%)38.4 V15.88 V (33.09%)2166.8 WDrop High
185 mm²353 A275 A7.81 V (16.27%)40.2 V12.88 V (26.83%)1756.8 WDrop High
240 mm²415 A324 A6.02 V (12.54%)42.0 V9.93 V (20.68%)1354.2 WDrop High
300 mm²477 A372 A4.81 V (10.03%)43.2 V7.94 V (16.55%)1083.4 WDrop High
400 mm²570 A445 A3.61 V (7.52%)44.4 V5.96 V (12.41%)812.5 WDrop High

FAQ — 225 Amp Cable Size at 150 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 225A at 150 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 225A over 150m at 48V (voltage drop: 1.2V or 2.51%).

What is the power capacity of 225A at 48V?

At unity power factor, 225A at 48V supports 10.8 kW with a standard 225A circuit breaker.