225 Amp Cable Size at 175 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 5.62V (2.44%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.95V (3.02%)
Voltage at Load224.4 VLine Loss: 1263.9 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1123.5 V (488.48%)0.0 V1853.25 V (805.76%)252787.5 WDrop High
2.5 mm²24 A18 A674.1 V (293.09%)0.0 V1111.95 V (483.46%)151672.5 WDrop High
4 mm²32 A25 A421.31 V (183.18%)0.0 V694.97 V (302.16%)94795.3 WDrop High
6 mm²41 A32 A280.88 V (122.12%)0.0 V463.31 V (201.44%)63196.9 WDrop High
10 mm²57 A44 A168.52 V (73.27%)61.5 V277.99 V (120.86%)37918.1 WDrop High
16 mm²76 A59 A105.33 V (45.79%)124.7 V173.74 V (75.54%)23698.8 WDrop High
25 mm²101 A78 A67.41 V (29.31%)162.6 V111.19 V (48.35%)15167.2 WDrop High
35 mm²125 A97 A48.15 V (20.93%)181.9 V79.42 V (34.53%)10833.7 WDrop High
50 mm²151 A118 A33.7 V (14.65%)196.3 V55.6 V (24.17%)7583.6 WDrop High
70 mm²192 A150 A24.07 V (10.47%)205.9 V39.71 V (17.27%)5416.9 WDrop High
95 mm²232 A181 A17.74 V (7.71%)212.3 V29.26 V (12.72%)3991.4 WDrop High
120 mm²269 A210 A14.04 V (6.11%)216.0 V23.17 V (10.07%)3159.8 WDrop High
150 mm²309 A241 A11.23 V (4.88%)218.8 V18.53 V (8.06%)2527.9 W~ ≤5%
185 mm²353 A275 A9.11 V (3.96%)220.9 V15.03 V (6.53%)2049.6 W~ ≤5%
240 mm²415 A324 A7.02 V (3.05%)223.0 V11.58 V (5.04%)1579.9 W~ ≤5%
300 mm²477 A372 A5.62 V (2.44%)224.4 V9.27 V (4.03%)1263.9 W✓ OK (≤3%)
400 mm²570 A445 A4.21 V (1.83%)225.8 V6.95 V (3.02%)948.0 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 175 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 225A at 175 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 225A over 175m at 230V (voltage drop: 5.62V or 2.44%).

What is the power capacity of 225A at 230V?

At unity power factor, 225A at 230V supports 51.75 kW with a standard 225A circuit breaker.