⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

225 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 0.51V (2.11%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 0.53V (2.21%)
Voltage at Load23.5 VLine Loss: 114.0 W
Max Power & Breaker5.4 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A32.1 V (133.75%)0.0 V52.95 V (220.62%)7222.5 WDrop High
2.5 mm²24 A18 A19.26 V (80.25%)4.7 V31.77 V (132.38%)4333.5 WDrop High
4 mm²32 A25 A12.04 V (50.16%)12.0 V19.86 V (82.73%)2708.4 WDrop High
6 mm²41 A32 A8.03 V (33.44%)16.0 V13.24 V (55.16%)1805.6 WDrop High
10 mm²57 A44 A4.81 V (20.06%)19.2 V7.94 V (33.09%)1083.4 WDrop High
16 mm²76 A59 A3.01 V (12.54%)21.0 V4.96 V (20.68%)677.1 WDrop High
25 mm²101 A78 A1.93 V (8.03%)22.1 V3.18 V (13.24%)433.4 WDrop High
35 mm²125 A97 A1.38 V (5.73%)22.6 V2.27 V (9.46%)309.5 WDrop High
50 mm²151 A118 A0.96 V (4.01%)23.0 V1.59 V (6.62%)216.7 WDrop High
70 mm²192 A150 A0.69 V (2.87%)23.3 V1.13 V (4.73%)154.8 WDrop High
95 mm²232 A181 A0.51 V (2.11%)23.5 V0.84 V (3.48%)114.0 W✓ OK (≤3%)
120 mm²269 A210 A0.4 V (1.67%)23.6 V0.66 V (2.76%)90.3 W✓ OK (≤3%)
150 mm²309 A241 A0.32 V (1.34%)23.7 V0.53 V (2.21%)72.2 W✓ OK (≤3%)
185 mm²353 A275 A0.26 V (1.08%)23.7 V0.43 V (1.79%)58.6 W✓ OK (≤3%)
240 mm²415 A324 A0.2 V (0.84%)23.8 V0.33 V (1.38%)45.1 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.67%)23.8 V0.26 V (1.1%)36.1 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.5%)23.9 V0.2 V (0.83%)27.1 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 225A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 225A over 5m at 24V (voltage drop: 0.51V or 2.11%).

What is the power capacity of 225A at 24V?

At unity power factor, 225A at 24V supports 5.4 kW with a standard 225A circuit breaker.