225 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 600 m (1968.5 ft).
Copper Cable (≤3% Drop)3× 400 mm²Drop: 4.81V (2.09%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 23.83V (10.36%)
Voltage at Load225.2 VLine Loss: 1083.4 W
Max Power & Breaker51.75 kW225A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 3852.0 V (1674.78%) | 0.0 V | 6354.0 V (2762.61%) | 866700.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 2311.2 V (1004.87%) | 0.0 V | 3812.4 V (1657.57%) | 520020.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1444.5 V (628.04%) | 0.0 V | 2382.75 V (1035.98%) | 325012.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 963.0 V (418.7%) | 0.0 V | 1588.5 V (690.65%) | 216675.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 577.8 V (251.22%) | 0.0 V | 953.1 V (414.39%) | 130005.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 361.12 V (157.01%) | 0.0 V | 595.69 V (258.99%) | 81253.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 231.12 V (100.49%) | 0.0 V | 381.24 V (165.76%) | 52002.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 165.09 V (71.78%) | 64.9 V | 272.31 V (118.4%) | 37144.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 115.56 V (50.24%) | 114.4 V | 190.62 V (82.88%) | 26001.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 82.54 V (35.89%) | 147.5 V | 136.16 V (59.2%) | 18572.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 60.82 V (26.44%) | 169.2 V | 100.33 V (43.62%) | 13684.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 48.15 V (20.93%) | 181.8 V | 79.42 V (34.53%) | 10833.8 W | Drop High |
| 150 mm² | 309 A | 241 A | 38.52 V (16.75%) | 191.5 V | 63.54 V (27.63%) | 8667.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 31.23 V (13.58%) | 198.8 V | 51.52 V (22.4%) | 7027.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 24.07 V (10.47%) | 205.9 V | 39.71 V (17.27%) | 5416.9 W | Drop High |
| 300 mm² | 477 A | 372 A | 19.26 V (8.37%) | 210.7 V | 31.77 V (13.81%) | 4333.5 W | Drop High |
| 400 mm² | 570 A | 445 A | 14.44 V (6.28%) | 215.6 V | 23.83 V (10.36%) | 3250.1 W | Drop High |
FAQ — 225 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))
What mm² cable size is required for 225A at 600 meters (230V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 225A over 600m at 230V (voltage drop: 4.81V or 2.09%).
What is the power capacity of 225A at 230V?
At unity power factor, 225A at 230V supports 51.75 kW with a standard 225A circuit breaker.
Related Lengths & Currents (230V)
225A · 5m (230V)225A · 10m (230V)225A · 15m (230V)225A · 20m (230V)225A · 25m (230V)225A · 30m (230V)225A · 35m (230V)225A · 40m (230V)225A · 45m (230V)225A · 50m (230V)225A · 60m (230V)225A · 70m (230V)10A · 600m (230V)16A · 600m (230V)20A · 600m (230V)25A · 600m (230V)32A · 600m (230V)40A · 600m (230V)50A · 600m (230V)63A · 600m (230V)80A · 600m (230V)100A · 600m (230V)125A · 600m (230V)160A · 600m (230V)200A · 600m (230V)