32 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 600 m (1968.5 ft).
Copper Cable (≤3% Drop)120 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 5.65V (2.46%)
Voltage at Load223.2 VLine Loss: 219.1 W
Max Power & Breaker7.36 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 547.84 V (238.19%) | 0.0 V | 903.68 V (392.9%) | 17530.9 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 328.7 V (142.91%) | 0.0 V | 542.21 V (235.74%) | 10518.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 205.44 V (89.32%) | 24.6 V | 338.88 V (147.34%) | 6574.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 136.96 V (59.55%) | 93.0 V | 225.92 V (98.23%) | 4382.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 82.18 V (35.73%) | 147.8 V | 135.55 V (58.94%) | 2629.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 51.36 V (22.33%) | 178.6 V | 84.72 V (36.83%) | 1643.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 32.87 V (14.29%) | 197.1 V | 54.22 V (23.57%) | 1051.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 23.48 V (10.21%) | 206.5 V | 38.73 V (16.84%) | 751.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 16.44 V (7.15%) | 213.6 V | 27.11 V (11.79%) | 525.9 W | Drop High |
| 70 mm² | 192 A | 150 A | 11.74 V (5.1%) | 218.3 V | 19.36 V (8.42%) | 375.7 W | Drop High |
| 95 mm² | 232 A | 181 A | 8.65 V (3.76%) | 221.3 V | 14.27 V (6.2%) | 276.8 W | ~ ≤5% |
| 120 mm² | 269 A | 210 A | 6.85 V (2.98%) | 223.2 V | 11.3 V (4.91%) | 219.1 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 5.48 V (2.38%) | 224.5 V | 9.04 V (3.93%) | 175.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 4.44 V (1.93%) | 225.6 V | 7.33 V (3.19%) | 142.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 3.42 V (1.49%) | 226.6 V | 5.65 V (2.46%) | 109.6 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 2.74 V (1.19%) | 227.3 V | 4.52 V (1.96%) | 87.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 2.05 V (0.89%) | 227.9 V | 3.39 V (1.47%) | 65.7 W | ✓ OK (≤3%) |
FAQ — 32 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))
What mm² cable size is required for 32A at 600 meters (230V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 32A over 600m at 230V (voltage drop: 6.85V or 2.98%).
What is the power capacity of 32A at 230V?
At unity power factor, 32A at 230V supports 7.36 kW with a standard 32A circuit breaker.
Related Lengths & Currents (230V)
32A · 5m (230V)32A · 10m (230V)32A · 15m (230V)32A · 20m (230V)32A · 25m (230V)32A · 30m (230V)32A · 35m (230V)32A · 40m (230V)32A · 45m (230V)32A · 50m (230V)32A · 60m (230V)32A · 70m (230V)10A · 600m (230V)16A · 600m (230V)20A · 600m (230V)25A · 600m (230V)40A · 600m (230V)50A · 600m (230V)63A · 600m (230V)80A · 600m (230V)100A · 600m (230V)125A · 600m (230V)160A · 600m (230V)200A · 600m (230V)