25 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 8.69V (2.17%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 9.17V (2.29%)
Voltage at Load391.3 VLine Loss: 376.2 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A92.66 V (23.17%)307.3 V152.85 V (38.21%)4012.5 WDrop High
2.5 mm²24 A18 A55.6 V (13.9%)344.4 V91.71 V (22.93%)2407.5 WDrop High
4 mm²32 A25 A34.75 V (8.69%)365.3 V57.32 V (14.33%)1504.7 WDrop High
6 mm²41 A32 A23.17 V (5.79%)376.8 V38.21 V (9.55%)1003.1 WDrop High
10 mm²57 A44 A13.9 V (3.47%)386.1 V22.93 V (5.73%)601.9 W~ ≤5%
16 mm²76 A59 A8.69 V (2.17%)391.3 V14.33 V (3.58%)376.2 W✓ OK (≤3%)
25 mm²101 A78 A5.56 V (1.39%)394.4 V9.17 V (2.29%)240.7 W✓ OK (≤3%)
35 mm²125 A97 A3.97 V (0.99%)396.0 V6.55 V (1.64%)172.0 W✓ OK (≤3%)
50 mm²151 A118 A2.78 V (0.69%)397.2 V4.59 V (1.15%)120.4 W✓ OK (≤3%)
70 mm²192 A150 A1.99 V (0.5%)398.0 V3.28 V (0.82%)86.0 W✓ OK (≤3%)
95 mm²232 A181 A1.46 V (0.37%)398.5 V2.41 V (0.6%)63.4 W✓ OK (≤3%)
120 mm²269 A210 A1.16 V (0.29%)398.8 V1.91 V (0.48%)50.2 W✓ OK (≤3%)
150 mm²309 A241 A0.93 V (0.23%)399.1 V1.53 V (0.38%)40.1 W✓ OK (≤3%)
185 mm²353 A275 A0.75 V (0.19%)399.2 V1.24 V (0.31%)32.5 W✓ OK (≤3%)
240 mm²415 A324 A0.58 V (0.14%)399.4 V0.96 V (0.24%)25.1 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (0.12%)399.5 V0.76 V (0.19%)20.1 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (0.09%)399.7 V0.57 V (0.14%)15.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 25A at 150 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 25A over 150m at 400V (voltage drop: 8.69V or 2.17%).

What is the power capacity of 25A at 400V?

At unity power factor, 25A at 400V supports 17.32 kW with a standard 25A circuit breaker.