⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

40 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 10.48V (2.62%)
Voltage at Load391.1 VLine Loss: 616.3 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A148.26 V (37.07%)251.7 V244.57 V (61.14%)10272.0 WDrop High
2.5 mm²24 A18 A88.96 V (22.24%)311.0 V146.74 V (36.68%)6163.2 WDrop High
4 mm²32 A25 A55.6 V (13.9%)344.4 V91.71 V (22.93%)3852.0 WDrop High
6 mm²41 A32 A37.07 V (9.27%)362.9 V61.14 V (15.29%)2568.0 WDrop High
10 mm²57 A44 A22.24 V (5.56%)377.8 V36.68 V (9.17%)1540.8 WDrop High
16 mm²76 A59 A13.9 V (3.47%)386.1 V22.93 V (5.73%)963.0 W~ ≤5%
25 mm²101 A78 A8.9 V (2.22%)391.1 V14.67 V (3.67%)616.3 W✓ OK (≤3%)
35 mm²125 A97 A6.35 V (1.59%)393.6 V10.48 V (2.62%)440.2 W✓ OK (≤3%)
50 mm²151 A118 A4.45 V (1.11%)395.6 V7.34 V (1.83%)308.2 W✓ OK (≤3%)
70 mm²192 A150 A3.18 V (0.79%)396.8 V5.24 V (1.31%)220.1 W✓ OK (≤3%)
95 mm²232 A181 A2.34 V (0.59%)397.7 V3.86 V (0.97%)162.2 W✓ OK (≤3%)
120 mm²269 A210 A1.85 V (0.46%)398.1 V3.06 V (0.76%)128.4 W✓ OK (≤3%)
150 mm²309 A241 A1.48 V (0.37%)398.5 V2.45 V (0.61%)102.7 W✓ OK (≤3%)
185 mm²353 A275 A1.2 V (0.3%)398.8 V1.98 V (0.5%)83.3 W✓ OK (≤3%)
240 mm²415 A324 A0.93 V (0.23%)399.1 V1.53 V (0.38%)64.2 W✓ OK (≤3%)
300 mm²477 A372 A0.74 V (0.19%)399.3 V1.22 V (0.31%)51.4 W✓ OK (≤3%)
400 mm²570 A445 A0.56 V (0.14%)399.4 V0.92 V (0.23%)38.5 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 150 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 40A at 150 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 40A over 150m at 400V (voltage drop: 8.9V or 2.22%).

What is the power capacity of 40A at 400V?

At unity power factor, 40A at 400V supports 27.71 kW with a standard 40A circuit breaker.