⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 50 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.52V (2.4%)
Voltage at Load224.7 VLine Loss: 133.7 W
Max Power & Breaker5.75 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A35.67 V (15.51%)194.3 V58.83 V (25.58%)891.7 WDrop High
2.5 mm²24 A18 A21.4 V (9.3%)208.6 V35.3 V (15.35%)535.0 WDrop High
4 mm²32 A25 A13.37 V (5.82%)216.6 V22.06 V (9.59%)334.4 WDrop High
6 mm²41 A32 A8.92 V (3.88%)221.1 V14.71 V (6.39%)222.9 W~ ≤5%
10 mm²57 A44 A5.35 V (2.33%)224.7 V8.82 V (3.84%)133.7 W✓ OK (≤3%)
16 mm²76 A59 A3.34 V (1.45%)226.7 V5.52 V (2.4%)83.6 W✓ OK (≤3%)
25 mm²101 A78 A2.14 V (0.93%)227.9 V3.53 V (1.53%)53.5 W✓ OK (≤3%)
35 mm²125 A97 A1.53 V (0.66%)228.5 V2.52 V (1.1%)38.2 W✓ OK (≤3%)
50 mm²151 A118 A1.07 V (0.47%)228.9 V1.76 V (0.77%)26.7 W✓ OK (≤3%)
70 mm²192 A150 A0.76 V (0.33%)229.2 V1.26 V (0.55%)19.1 W✓ OK (≤3%)
95 mm²232 A181 A0.56 V (0.24%)229.4 V0.93 V (0.4%)14.1 W✓ OK (≤3%)
120 mm²269 A210 A0.45 V (0.19%)229.6 V0.74 V (0.32%)11.1 W✓ OK (≤3%)
150 mm²309 A241 A0.36 V (0.16%)229.6 V0.59 V (0.26%)8.9 W✓ OK (≤3%)
185 mm²353 A275 A0.29 V (0.13%)229.7 V0.48 V (0.21%)7.2 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.1%)229.8 V0.37 V (0.16%)5.6 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.08%)229.8 V0.29 V (0.13%)4.5 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.06%)229.9 V0.22 V (0.1%)3.3 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 50 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 25A at 50 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 25A over 50m at 230V (voltage drop: 5.35V or 2.33%).

What is the power capacity of 25A at 230V?

At unity power factor, 25A at 230V supports 5.75 kW with a standard 25A circuit breaker.