25 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 4.81V (2.09%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 4.96V (2.16%)
Voltage at Load225.2 VLine Loss: 120.4 W
Max Power & Breaker5.75 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A32.1 V (13.96%)197.9 V52.95 V (23.02%)802.5 WDrop High
2.5 mm²24 A18 A19.26 V (8.37%)210.7 V31.77 V (13.81%)481.5 WDrop High
4 mm²32 A25 A12.04 V (5.23%)218.0 V19.86 V (8.63%)300.9 WDrop High
6 mm²41 A32 A8.03 V (3.49%)222.0 V13.24 V (5.76%)200.6 W~ ≤5%
10 mm²57 A44 A4.81 V (2.09%)225.2 V7.94 V (3.45%)120.4 W✓ OK (≤3%)
16 mm²76 A59 A3.01 V (1.31%)227.0 V4.96 V (2.16%)75.2 W✓ OK (≤3%)
25 mm²101 A78 A1.93 V (0.84%)228.1 V3.18 V (1.38%)48.1 W✓ OK (≤3%)
35 mm²125 A97 A1.38 V (0.6%)228.6 V2.27 V (0.99%)34.4 W✓ OK (≤3%)
50 mm²151 A118 A0.96 V (0.42%)229.0 V1.59 V (0.69%)24.1 W✓ OK (≤3%)
70 mm²192 A150 A0.69 V (0.3%)229.3 V1.13 V (0.49%)17.2 W✓ OK (≤3%)
95 mm²232 A181 A0.51 V (0.22%)229.5 V0.84 V (0.36%)12.7 W✓ OK (≤3%)
120 mm²269 A210 A0.4 V (0.17%)229.6 V0.66 V (0.29%)10.0 W✓ OK (≤3%)
150 mm²309 A241 A0.32 V (0.14%)229.7 V0.53 V (0.23%)8.0 W✓ OK (≤3%)
185 mm²353 A275 A0.26 V (0.11%)229.7 V0.43 V (0.19%)6.5 W✓ OK (≤3%)
240 mm²415 A324 A0.2 V (0.09%)229.8 V0.33 V (0.14%)5.0 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.07%)229.8 V0.26 V (0.12%)4.0 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.05%)229.9 V0.2 V (0.09%)3.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 45 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 25A at 45 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 25A over 45m at 230V (voltage drop: 4.81V or 2.09%).

What is the power capacity of 25A at 230V?

At unity power factor, 25A at 230V supports 5.75 kW with a standard 25A circuit breaker.