30 Amp Cable Size at 80 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.17V (2.29%)
Voltage at Load391.1 VLine Loss: 462.2 W
Max Power & Breaker20.78 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A59.31 V (14.83%)340.7 V97.83 V (24.46%)3081.6 WDrop High
2.5 mm²24 A18 A35.58 V (8.9%)364.4 V58.7 V (14.67%)1849.0 WDrop High
4 mm²32 A25 A22.24 V (5.56%)377.8 V36.68 V (9.17%)1155.6 WDrop High
6 mm²41 A32 A14.83 V (3.71%)385.2 V24.46 V (6.11%)770.4 W~ ≤5%
10 mm²57 A44 A8.9 V (2.22%)391.1 V14.67 V (3.67%)462.2 W✓ OK (≤3%)
16 mm²76 A59 A5.56 V (1.39%)394.4 V9.17 V (2.29%)288.9 W✓ OK (≤3%)
25 mm²101 A78 A3.56 V (0.89%)396.4 V5.87 V (1.47%)184.9 W✓ OK (≤3%)
35 mm²125 A97 A2.54 V (0.64%)397.5 V4.19 V (1.05%)132.1 W✓ OK (≤3%)
50 mm²151 A118 A1.78 V (0.44%)398.2 V2.93 V (0.73%)92.4 W✓ OK (≤3%)
70 mm²192 A150 A1.27 V (0.32%)398.7 V2.1 V (0.52%)66.0 W✓ OK (≤3%)
95 mm²232 A181 A0.94 V (0.23%)399.1 V1.54 V (0.39%)48.7 W✓ OK (≤3%)
120 mm²269 A210 A0.74 V (0.19%)399.3 V1.22 V (0.31%)38.5 W✓ OK (≤3%)
150 mm²309 A241 A0.59 V (0.15%)399.4 V0.98 V (0.24%)30.8 W✓ OK (≤3%)
185 mm²353 A275 A0.48 V (0.12%)399.5 V0.79 V (0.2%)25.0 W✓ OK (≤3%)
240 mm²415 A324 A0.37 V (0.09%)399.6 V0.61 V (0.15%)19.3 W✓ OK (≤3%)
300 mm²477 A372 A0.3 V (0.07%)399.7 V0.49 V (0.12%)15.4 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.06%)399.8 V0.37 V (0.09%)11.6 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 80 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 30A at 80 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 30A over 80m at 400V (voltage drop: 8.9V or 2.22%).

What is the power capacity of 30A at 400V?

At unity power factor, 30A at 400V supports 20.78 kW with a standard 30A circuit breaker.