32 Amp Cable Size at 80 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 9.49V (2.37%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.78V (2.45%)
Voltage at Load390.5 VLine Loss: 525.9 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A63.26 V (15.81%)336.7 V104.35 V (26.09%)3506.2 WDrop High
2.5 mm²24 A18 A37.96 V (9.49%)362.0 V62.61 V (15.65%)2103.7 WDrop High
4 mm²32 A25 A23.72 V (5.93%)376.3 V39.13 V (9.78%)1314.8 WDrop High
6 mm²41 A32 A15.81 V (3.95%)384.2 V26.09 V (6.52%)876.5 W~ ≤5%
10 mm²57 A44 A9.49 V (2.37%)390.5 V15.65 V (3.91%)525.9 W✓ OK (≤3%)
16 mm²76 A59 A5.93 V (1.48%)394.1 V9.78 V (2.45%)328.7 W✓ OK (≤3%)
25 mm²101 A78 A3.8 V (0.95%)396.2 V6.26 V (1.57%)210.4 W✓ OK (≤3%)
35 mm²125 A97 A2.71 V (0.68%)397.3 V4.47 V (1.12%)150.3 W✓ OK (≤3%)
50 mm²151 A118 A1.9 V (0.47%)398.1 V3.13 V (0.78%)105.2 W✓ OK (≤3%)
70 mm²192 A150 A1.36 V (0.34%)398.6 V2.24 V (0.56%)75.1 W✓ OK (≤3%)
95 mm²232 A181 A1.0 V (0.25%)399.0 V1.65 V (0.41%)55.4 W✓ OK (≤3%)
120 mm²269 A210 A0.79 V (0.2%)399.2 V1.3 V (0.33%)43.8 W✓ OK (≤3%)
150 mm²309 A241 A0.63 V (0.16%)399.4 V1.04 V (0.26%)35.1 W✓ OK (≤3%)
185 mm²353 A275 A0.51 V (0.13%)399.5 V0.85 V (0.21%)28.4 W✓ OK (≤3%)
240 mm²415 A324 A0.4 V (0.1%)399.6 V0.65 V (0.16%)21.9 W✓ OK (≤3%)
300 mm²477 A372 A0.32 V (0.08%)399.7 V0.52 V (0.13%)17.5 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (0.06%)399.8 V0.39 V (0.1%)13.1 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 80 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 32A at 80 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 32A over 80m at 400V (voltage drop: 9.49V or 2.37%).

What is the power capacity of 32A at 400V?

At unity power factor, 32A at 400V supports 22.17 kW with a standard 32A circuit breaker.