300 Amp Cable Size at 300 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)7× 400 mm²Drop: 1.38V (2.87%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 15.88V (33.09%)
Voltage at Load46.6 VLine Loss: 412.7 W
Max Power & Breaker14.4 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2568.0 V (5350.0%)0.0 V4236.0 V (8825.0%)770400.0 WDrop High
2.5 mm²24 A18 A1540.8 V (3210.0%)0.0 V2541.6 V (5295.0%)462240.0 WDrop High
4 mm²32 A25 A963.0 V (2006.25%)0.0 V1588.5 V (3309.38%)288900.0 WDrop High
6 mm²41 A32 A642.0 V (1337.5%)0.0 V1059.0 V (2206.25%)192600.0 WDrop High
10 mm²57 A44 A385.2 V (802.5%)0.0 V635.4 V (1323.75%)115560.0 WDrop High
16 mm²76 A59 A240.75 V (501.56%)0.0 V397.12 V (827.34%)72225.0 WDrop High
25 mm²101 A78 A154.08 V (321.0%)0.0 V254.16 V (529.5%)46224.0 WDrop High
35 mm²125 A97 A110.06 V (229.29%)0.0 V181.54 V (378.21%)33017.1 WDrop High
50 mm²151 A118 A77.04 V (160.5%)0.0 V127.08 V (264.75%)23112.0 WDrop High
70 mm²192 A150 A55.03 V (114.64%)0.0 V90.77 V (189.11%)16508.6 WDrop High
95 mm²232 A181 A40.55 V (84.47%)7.5 V66.88 V (139.34%)12164.2 WDrop High
120 mm²269 A210 A32.1 V (66.88%)15.9 V52.95 V (110.31%)9630.0 WDrop High
150 mm²309 A241 A25.68 V (53.5%)22.3 V42.36 V (88.25%)7704.0 WDrop High
185 mm²353 A275 A20.82 V (43.38%)27.2 V34.35 V (71.55%)6246.5 WDrop High
240 mm²415 A324 A16.05 V (33.44%)31.9 V26.47 V (55.16%)4815.0 WDrop High
300 mm²477 A372 A12.84 V (26.75%)35.2 V21.18 V (44.12%)3852.0 WDrop High
400 mm²570 A445 A9.63 V (20.06%)38.4 V15.88 V (33.09%)2889.0 WDrop High

FAQ — 300 Amp Cable Size at 300 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 300A at 300 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 7× 400 mm² copper cable for 300A over 300m at 48V (voltage drop: 1.38V or 2.87%).

What is the power capacity of 300A at 48V?

At unity power factor, 300A at 48V supports 14.4 kW with a standard 300A circuit breaker.