300 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 0.43V (0.89%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.44V (0.92%)
Voltage at Load47.6 VLine Loss: 128.4 W
Max Power & Breaker14.4 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A42.8 V (89.17%)5.2 V70.6 V (147.08%)12840.0 WDrop High
2.5 mm²24 A18 A25.68 V (53.5%)22.3 V42.36 V (88.25%)7704.0 WDrop High
4 mm²32 A25 A16.05 V (33.44%)31.9 V26.47 V (55.16%)4815.0 WDrop High
6 mm²41 A32 A10.7 V (22.29%)37.3 V17.65 V (36.77%)3210.0 WDrop High
10 mm²57 A44 A6.42 V (13.38%)41.6 V10.59 V (22.06%)1926.0 WDrop High
16 mm²76 A59 A4.01 V (8.36%)44.0 V6.62 V (13.79%)1203.8 WDrop High
25 mm²101 A78 A2.57 V (5.35%)45.4 V4.24 V (8.82%)770.4 WDrop High
35 mm²125 A97 A1.83 V (3.82%)46.2 V3.03 V (6.3%)550.3 WDrop High
50 mm²151 A118 A1.28 V (2.67%)46.7 V2.12 V (4.41%)385.2 WDrop High
70 mm²192 A150 A0.92 V (1.91%)47.1 V1.51 V (3.15%)275.1 WDrop High
95 mm²232 A181 A0.68 V (1.41%)47.3 V1.11 V (2.32%)202.7 WDrop High
120 mm²269 A210 A0.54 V (1.11%)47.5 V0.88 V (1.84%)160.5 WDrop High
150 mm²309 A241 A0.43 V (0.89%)47.6 V0.71 V (1.47%)128.4 W✓ OK (≤3%)
185 mm²353 A275 A0.35 V (0.72%)47.7 V0.57 V (1.19%)104.1 W✓ OK (≤3%)
240 mm²415 A324 A0.27 V (0.56%)47.7 V0.44 V (0.92%)80.2 W✓ OK (≤3%)
300 mm²477 A372 A0.21 V (0.45%)47.8 V0.35 V (0.74%)64.2 W✓ OK (≤3%)
400 mm²570 A445 A0.16 V (0.33%)47.8 V0.26 V (0.55%)48.1 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 300A at 5 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 5m at 48V (voltage drop: 0.43V or 0.89%).

What is the power capacity of 300A at 48V?

At unity power factor, 300A at 48V supports 14.4 kW with a standard 300A circuit breaker.