32 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 8.9V (2.14%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 9.39V (2.26%)
Voltage at Load406.1 VLine Loss: 493.1 W
Max Power & Breaker23.0 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A94.89 V (22.86%)320.1 V156.52 V (37.72%)5259.3 WDrop High
2.5 mm²24 A18 A56.93 V (13.72%)358.1 V93.91 V (22.63%)3155.6 WDrop High
4 mm²32 A25 A35.58 V (8.57%)379.4 V58.7 V (14.14%)1972.2 WDrop High
6 mm²41 A32 A23.72 V (5.72%)391.3 V39.13 V (9.43%)1314.8 WDrop High
10 mm²57 A44 A14.23 V (3.43%)400.8 V23.48 V (5.66%)788.9 W~ ≤5%
16 mm²76 A59 A8.9 V (2.14%)406.1 V14.67 V (3.54%)493.1 W✓ OK (≤3%)
25 mm²101 A78 A5.69 V (1.37%)409.3 V9.39 V (2.26%)315.6 W✓ OK (≤3%)
35 mm²125 A97 A4.07 V (0.98%)410.9 V6.71 V (1.62%)225.4 W✓ OK (≤3%)
50 mm²151 A118 A2.85 V (0.69%)412.2 V4.7 V (1.13%)157.8 W✓ OK (≤3%)
70 mm²192 A150 A2.03 V (0.49%)413.0 V3.35 V (0.81%)112.7 W✓ OK (≤3%)
95 mm²232 A181 A1.5 V (0.36%)413.5 V2.47 V (0.6%)83.0 W✓ OK (≤3%)
120 mm²269 A210 A1.19 V (0.29%)413.8 V1.96 V (0.47%)65.7 W✓ OK (≤3%)
150 mm²309 A241 A0.95 V (0.23%)414.1 V1.57 V (0.38%)52.6 W✓ OK (≤3%)
185 mm²353 A275 A0.77 V (0.19%)414.2 V1.27 V (0.31%)42.6 W✓ OK (≤3%)
240 mm²415 A324 A0.59 V (0.14%)414.4 V0.98 V (0.24%)32.9 W✓ OK (≤3%)
300 mm²477 A372 A0.47 V (0.11%)414.5 V0.78 V (0.19%)26.3 W✓ OK (≤3%)
400 mm²570 A445 A0.36 V (0.09%)414.6 V0.59 V (0.14%)19.7 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 32A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 32A over 120m at 415V (voltage drop: 8.9V or 2.14%).

What is the power capacity of 32A at 415V?

At unity power factor, 32A at 415V supports 23.0 kW with a standard 32A circuit breaker.