16 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 11.86V (2.86%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 11.74V (2.83%)
Voltage at Load403.1 VLine Loss: 328.7 W
Max Power & Breaker11.5 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A47.44 V (11.43%)367.6 V78.26 V (18.86%)1314.8 WDrop High
2.5 mm²24 A18 A28.47 V (6.86%)386.5 V46.96 V (11.31%)788.9 WDrop High
4 mm²32 A25 A17.79 V (4.29%)397.2 V29.35 V (7.07%)493.1 W~ ≤5%
6 mm²41 A32 A11.86 V (2.86%)403.1 V19.57 V (4.71%)328.7 W✓ OK (≤3%)
10 mm²57 A44 A7.12 V (1.71%)407.9 V11.74 V (2.83%)197.2 W✓ OK (≤3%)
16 mm²76 A59 A4.45 V (1.07%)410.6 V7.34 V (1.77%)123.3 W✓ OK (≤3%)
25 mm²101 A78 A2.85 V (0.69%)412.2 V4.7 V (1.13%)78.9 W✓ OK (≤3%)
35 mm²125 A97 A2.03 V (0.49%)413.0 V3.35 V (0.81%)56.3 W✓ OK (≤3%)
50 mm²151 A118 A1.42 V (0.34%)413.6 V2.35 V (0.57%)39.4 W✓ OK (≤3%)
70 mm²192 A150 A1.02 V (0.24%)414.0 V1.68 V (0.4%)28.2 W✓ OK (≤3%)
95 mm²232 A181 A0.75 V (0.18%)414.3 V1.24 V (0.3%)20.8 W✓ OK (≤3%)
120 mm²269 A210 A0.59 V (0.14%)414.4 V0.98 V (0.24%)16.4 W✓ OK (≤3%)
150 mm²309 A241 A0.47 V (0.11%)414.5 V0.78 V (0.19%)13.1 W✓ OK (≤3%)
185 mm²353 A275 A0.38 V (0.09%)414.6 V0.63 V (0.15%)10.7 W✓ OK (≤3%)
240 mm²415 A324 A0.3 V (0.07%)414.7 V0.49 V (0.12%)8.2 W✓ OK (≤3%)
300 mm²477 A372 A0.24 V (0.06%)414.8 V0.39 V (0.09%)6.6 W✓ OK (≤3%)
400 mm²570 A445 A0.18 V (0.04%)414.8 V0.29 V (0.07%)4.9 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 16A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 16A over 120m at 415V (voltage drop: 11.86V or 2.86%).

What is the power capacity of 16A at 415V?

At unity power factor, 16A at 415V supports 11.5 kW with a standard 16A circuit breaker.