32 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.59V (2.47%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.6V (2.51%)
Voltage at Load23.4 VLine Loss: 19.0 W
Max Power & Breaker0.77 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A73.05 V (304.36%)0.0 V120.49 V (502.04%)2337.5 WDrop High
2.5 mm²24 A18 A43.83 V (182.61%)0.0 V72.29 V (301.23%)1402.5 WDrop High
4 mm²32 A25 A27.39 V (114.13%)0.0 V45.18 V (188.27%)876.5 WDrop High
6 mm²41 A32 A18.26 V (76.09%)5.7 V30.12 V (125.51%)584.4 WDrop High
10 mm²57 A44 A10.96 V (45.65%)13.0 V18.07 V (75.31%)350.6 WDrop High
16 mm²76 A59 A6.85 V (28.53%)17.2 V11.3 V (47.07%)219.1 WDrop High
25 mm²101 A78 A4.38 V (18.26%)19.6 V7.23 V (30.12%)140.2 WDrop High
35 mm²125 A97 A3.13 V (13.04%)20.9 V5.16 V (21.52%)100.2 WDrop High
50 mm²151 A118 A2.19 V (9.13%)21.8 V3.61 V (15.06%)70.1 WDrop High
70 mm²192 A150 A1.57 V (6.52%)22.4 V2.58 V (10.76%)50.1 WDrop High
95 mm²232 A181 A1.15 V (4.81%)22.8 V1.9 V (7.93%)36.9 W~ ≤5%
120 mm²269 A210 A0.91 V (3.8%)23.1 V1.51 V (6.28%)29.2 W~ ≤5%
150 mm²309 A241 A0.73 V (3.04%)23.3 V1.2 V (5.02%)23.4 W~ ≤5%
185 mm²353 A275 A0.59 V (2.47%)23.4 V0.98 V (4.07%)19.0 W✓ OK (≤3%)
240 mm²415 A324 A0.46 V (1.9%)23.5 V0.75 V (3.14%)14.6 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (1.52%)23.6 V0.6 V (2.51%)11.7 W✓ OK (≤3%)
400 mm²570 A445 A0.27 V (1.14%)23.7 V0.45 V (1.88%)8.8 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 32A at 80 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 32A over 80m at 24V (voltage drop: 0.59V or 2.47%).

What is the power capacity of 32A at 24V?

At unity power factor, 32A at 24V supports 0.77 kW with a standard 32A circuit breaker.