200 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 80 m (262.5 ft).
Copper Cable (≤3% Drop)3× 400 mm²Drop: 0.57V (2.38%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.82V (11.77%)
Voltage at Load23.4 VLine Loss: 114.1 W
Max Power & Breaker4.8 kW200A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 80m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 456.53 V (1902.22%) | 0.0 V | 753.07 V (3137.78%) | 91306.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 273.92 V (1141.33%) | 0.0 V | 451.84 V (1882.67%) | 54784.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 171.2 V (713.33%) | 0.0 V | 282.4 V (1176.67%) | 34240.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 114.13 V (475.56%) | 0.0 V | 188.27 V (784.44%) | 22826.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 68.48 V (285.33%) | 0.0 V | 112.96 V (470.67%) | 13696.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 42.8 V (178.33%) | 0.0 V | 70.6 V (294.17%) | 8560.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 27.39 V (114.13%) | 0.0 V | 45.18 V (188.27%) | 5478.4 W | Drop High |
| 35 mm² | 125 A | 97 A | 19.57 V (81.52%) | 4.4 V | 32.27 V (134.48%) | 3913.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 13.7 V (57.07%) | 10.3 V | 22.59 V (94.13%) | 2739.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 9.78 V (40.76%) | 14.2 V | 16.14 V (67.24%) | 1956.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 7.21 V (30.04%) | 16.8 V | 11.89 V (49.54%) | 1441.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 5.71 V (23.78%) | 18.3 V | 9.41 V (39.22%) | 1141.3 W | Drop High |
| 150 mm² | 309 A | 241 A | 4.57 V (19.02%) | 19.4 V | 7.53 V (31.38%) | 913.1 W | Drop High |
| 185 mm² | 353 A | 275 A | 3.7 V (15.42%) | 20.3 V | 6.11 V (25.44%) | 740.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 2.85 V (11.89%) | 21.1 V | 4.71 V (19.61%) | 570.7 W | Drop High |
| 300 mm² | 477 A | 372 A | 2.28 V (9.51%) | 21.7 V | 3.77 V (15.69%) | 456.5 W | Drop High |
| 400 mm² | 570 A | 445 A | 1.71 V (7.13%) | 22.3 V | 2.82 V (11.77%) | 342.4 W | Drop High |
FAQ — 200 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))
What mm² cable size is required for 200A at 80 meters (24V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 200A over 80m at 24V (voltage drop: 0.57V or 2.38%).
What is the power capacity of 200A at 24V?
At unity power factor, 200A at 24V supports 4.8 kW with a standard 200A circuit breaker.
Related Lengths & Currents (24V)
200A · 5m (24V)200A · 10m (24V)200A · 15m (24V)200A · 20m (24V)200A · 25m (24V)200A · 30m (24V)200A · 35m (24V)200A · 40m (24V)200A · 45m (24V)200A · 50m (24V)200A · 60m (24V)200A · 70m (24V)10A · 80m (24V)16A · 80m (24V)20A · 80m (24V)25A · 80m (24V)32A · 80m (24V)40A · 80m (24V)50A · 80m (24V)63A · 80m (24V)80A · 80m (24V)100A · 80m (24V)125A · 80m (24V)160A · 80m (24V)