200 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 0.57V (2.38%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.82V (11.77%)
Voltage at Load23.4 VLine Loss: 114.1 W
Max Power & Breaker4.8 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A456.53 V (1902.22%)0.0 V753.07 V (3137.78%)91306.7 WDrop High
2.5 mm²24 A18 A273.92 V (1141.33%)0.0 V451.84 V (1882.67%)54784.0 WDrop High
4 mm²32 A25 A171.2 V (713.33%)0.0 V282.4 V (1176.67%)34240.0 WDrop High
6 mm²41 A32 A114.13 V (475.56%)0.0 V188.27 V (784.44%)22826.7 WDrop High
10 mm²57 A44 A68.48 V (285.33%)0.0 V112.96 V (470.67%)13696.0 WDrop High
16 mm²76 A59 A42.8 V (178.33%)0.0 V70.6 V (294.17%)8560.0 WDrop High
25 mm²101 A78 A27.39 V (114.13%)0.0 V45.18 V (188.27%)5478.4 WDrop High
35 mm²125 A97 A19.57 V (81.52%)4.4 V32.27 V (134.48%)3913.1 WDrop High
50 mm²151 A118 A13.7 V (57.07%)10.3 V22.59 V (94.13%)2739.2 WDrop High
70 mm²192 A150 A9.78 V (40.76%)14.2 V16.14 V (67.24%)1956.6 WDrop High
95 mm²232 A181 A7.21 V (30.04%)16.8 V11.89 V (49.54%)1441.7 WDrop High
120 mm²269 A210 A5.71 V (23.78%)18.3 V9.41 V (39.22%)1141.3 WDrop High
150 mm²309 A241 A4.57 V (19.02%)19.4 V7.53 V (31.38%)913.1 WDrop High
185 mm²353 A275 A3.7 V (15.42%)20.3 V6.11 V (25.44%)740.3 WDrop High
240 mm²415 A324 A2.85 V (11.89%)21.1 V4.71 V (19.61%)570.7 WDrop High
300 mm²477 A372 A2.28 V (9.51%)21.7 V3.77 V (15.69%)456.5 WDrop High
400 mm²570 A445 A1.71 V (7.13%)22.3 V2.82 V (11.77%)342.4 WDrop High

FAQ — 200 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 200A at 80 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 200A over 80m at 24V (voltage drop: 0.57V or 2.38%).

What is the power capacity of 200A at 24V?

At unity power factor, 200A at 24V supports 4.8 kW with a standard 200A circuit breaker.