35 Amp Cable Size at 20 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 4.99V (2.17%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 4.94V (2.15%)
Voltage at Load225.0 VLine Loss: 174.8 W
Max Power & Breaker8.05 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A19.97 V (8.68%)210.0 V32.95 V (14.32%)699.1 WDrop High
2.5 mm²24 A18 A11.98 V (5.21%)218.0 V19.77 V (8.59%)419.4 WDrop High
4 mm²32 A25 A7.49 V (3.26%)222.5 V12.35 V (5.37%)262.1 WDrop High
6 mm²41 A32 A4.99 V (2.17%)225.0 V8.24 V (3.58%)174.8 W✓ OK (≤3%)
10 mm²57 A44 A3.0 V (1.3%)227.0 V4.94 V (2.15%)104.9 W✓ OK (≤3%)
16 mm²76 A59 A1.87 V (0.81%)228.1 V3.09 V (1.34%)65.5 W✓ OK (≤3%)
25 mm²101 A78 A1.2 V (0.52%)228.8 V1.98 V (0.86%)41.9 W✓ OK (≤3%)
35 mm²125 A97 A0.86 V (0.37%)229.1 V1.41 V (0.61%)30.0 W✓ OK (≤3%)
50 mm²151 A118 A0.6 V (0.26%)229.4 V0.99 V (0.43%)21.0 W✓ OK (≤3%)
70 mm²192 A150 A0.43 V (0.19%)229.6 V0.71 V (0.31%)15.0 W✓ OK (≤3%)
95 mm²232 A181 A0.32 V (0.14%)229.7 V0.52 V (0.23%)11.0 W✓ OK (≤3%)
120 mm²269 A210 A0.25 V (0.11%)229.8 V0.41 V (0.18%)8.7 W✓ OK (≤3%)
150 mm²309 A241 A0.2 V (0.09%)229.8 V0.33 V (0.14%)7.0 W✓ OK (≤3%)
185 mm²353 A275 A0.16 V (0.07%)229.8 V0.27 V (0.12%)5.7 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.05%)229.9 V0.21 V (0.09%)4.4 W✓ OK (≤3%)
300 mm²477 A372 A0.1 V (0.04%)229.9 V0.16 V (0.07%)3.5 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.03%)229.9 V0.12 V (0.05%)2.6 W✓ OK (≤3%)

FAQ — 35 Amp Cable Size at 20 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 35A at 20 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 35A over 20m at 230V (voltage drop: 4.99V or 2.17%).

What is the power capacity of 35A at 230V?

At unity power factor, 35A at 230V supports 8.05 kW with a standard 35A circuit breaker.