35 Amp Cable Size at 35 Meters (230V Single-Phase (IEC Europe / UK / AU))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 35 A over 35 m (114.8 ft).
Copper Cable (≤3% Drop)10 mm²Drop: 5.24V (2.28%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.41V (2.35%)
Voltage at Load224.8 VLine Loss: 183.5 W
Max Power & Breaker8.05 kW35A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 34.95 V (15.2%) | 195.0 V | 57.66 V (25.07%) | 1223.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 20.97 V (9.12%) | 209.0 V | 34.59 V (15.04%) | 734.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 13.11 V (5.7%) | 216.9 V | 21.62 V (9.4%) | 458.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 8.74 V (3.8%) | 221.3 V | 14.41 V (6.27%) | 305.8 W | ~ ≤5% |
| 10 mm² | 57 A | 44 A | 5.24 V (2.28%) | 224.8 V | 8.65 V (3.76%) | 183.5 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 3.28 V (1.42%) | 226.7 V | 5.41 V (2.35%) | 114.7 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 2.1 V (0.91%) | 227.9 V | 3.46 V (1.5%) | 73.4 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 1.5 V (0.65%) | 228.5 V | 2.47 V (1.07%) | 52.4 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.05 V (0.46%) | 229.0 V | 1.73 V (0.75%) | 36.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.75 V (0.33%) | 229.3 V | 1.24 V (0.54%) | 26.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.55 V (0.24%) | 229.4 V | 0.91 V (0.4%) | 19.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.44 V (0.19%) | 229.6 V | 0.72 V (0.31%) | 15.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.35 V (0.15%) | 229.7 V | 0.58 V (0.25%) | 12.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.28 V (0.12%) | 229.7 V | 0.47 V (0.2%) | 9.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.22 V (0.09%) | 229.8 V | 0.36 V (0.16%) | 7.6 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.17 V (0.08%) | 229.8 V | 0.29 V (0.13%) | 6.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.13 V (0.06%) | 229.9 V | 0.22 V (0.09%) | 4.6 W | ✓ OK (≤3%) |
FAQ — 35 Amp Cable Size at 35 Meters (230V Single-Phase (IEC Europe / UK / AU))
What mm² cable size is required for 35A at 35 meters (230V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 35A over 35m at 230V (voltage drop: 5.24V or 2.28%).
What is the power capacity of 35A at 230V?
At unity power factor, 35A at 230V supports 8.05 kW with a standard 35A circuit breaker.
Related Lengths & Currents (230V)
35A · 5m (230V)35A · 10m (230V)35A · 15m (230V)35A · 20m (230V)35A · 25m (230V)35A · 30m (230V)35A · 40m (230V)35A · 45m (230V)35A · 50m (230V)35A · 60m (230V)35A · 70m (230V)10A · 35m (230V)16A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)100A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)