350 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.75V (0.44%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.78V (0.45%)
Voltage at Load398.2 VLine Loss: 1062.8 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A216.22 V (54.05%)183.8 V356.66 V (89.16%)131075.0 WDrop High
2.5 mm²24 A18 A129.73 V (32.43%)270.3 V213.99 V (53.5%)78645.0 WDrop High
4 mm²32 A25 A81.08 V (20.27%)318.9 V133.75 V (33.44%)49153.1 WDrop High
6 mm²41 A32 A54.05 V (13.51%)345.9 V89.16 V (22.29%)32768.8 WDrop High
10 mm²57 A44 A32.43 V (8.11%)367.6 V53.5 V (13.37%)19661.2 WDrop High
16 mm²76 A59 A20.27 V (5.07%)379.7 V33.44 V (8.36%)12288.3 WDrop High
25 mm²101 A78 A12.97 V (3.24%)387.0 V21.4 V (5.35%)7864.5 WDrop High
35 mm²125 A97 A9.27 V (2.32%)390.7 V15.29 V (3.82%)5617.5 WDrop High
50 mm²151 A118 A6.49 V (1.62%)393.5 V10.7 V (2.67%)3932.2 WDrop High
70 mm²192 A150 A4.63 V (1.16%)395.4 V7.64 V (1.91%)2808.7 WDrop High
95 mm²232 A181 A3.41 V (0.85%)396.6 V5.63 V (1.41%)2069.6 WDrop High
120 mm²269 A210 A2.7 V (0.68%)397.3 V4.46 V (1.11%)1638.4 WDrop High
150 mm²309 A241 A2.16 V (0.54%)397.8 V3.57 V (0.89%)1310.7 WDrop High
185 mm²353 A275 A1.75 V (0.44%)398.2 V2.89 V (0.72%)1062.8 W✓ OK (≤3%)
240 mm²415 A324 A1.35 V (0.34%)398.6 V2.23 V (0.56%)819.2 W✓ OK (≤3%)
300 mm²477 A372 A1.08 V (0.27%)398.9 V1.78 V (0.45%)655.4 W✓ OK (≤3%)
400 mm²570 A445 A0.81 V (0.2%)399.2 V1.34 V (0.33%)491.5 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 25 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 350A at 25 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 350A over 25m at 400V (voltage drop: 1.75V or 0.44%).

What is the power capacity of 350A at 400V?

At unity power factor, 350A at 400V supports 242.49 kW with a standard 350A circuit breaker.