350 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.35V (0.09%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.36V (0.09%)
Voltage at Load399.6 VLine Loss: 212.6 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A43.24 V (10.81%)356.8 V71.33 V (17.83%)26215.0 WDrop High
2.5 mm²24 A18 A25.95 V (6.49%)374.1 V42.8 V (10.7%)15729.0 WDrop High
4 mm²32 A25 A16.22 V (4.05%)383.8 V26.75 V (6.69%)9830.6 WDrop High
6 mm²41 A32 A10.81 V (2.7%)389.2 V17.83 V (4.46%)6553.8 WDrop High
10 mm²57 A44 A6.49 V (1.62%)393.5 V10.7 V (2.67%)3932.2 WDrop High
16 mm²76 A59 A4.05 V (1.01%)395.9 V6.69 V (1.67%)2457.7 WDrop High
25 mm²101 A78 A2.59 V (0.65%)397.4 V4.28 V (1.07%)1572.9 WDrop High
35 mm²125 A97 A1.85 V (0.46%)398.1 V3.06 V (0.76%)1123.5 WDrop High
50 mm²151 A118 A1.3 V (0.32%)398.7 V2.14 V (0.53%)786.5 WDrop High
70 mm²192 A150 A0.93 V (0.23%)399.1 V1.53 V (0.38%)561.8 WDrop High
95 mm²232 A181 A0.68 V (0.17%)399.3 V1.13 V (0.28%)413.9 WDrop High
120 mm²269 A210 A0.54 V (0.14%)399.5 V0.89 V (0.22%)327.7 WDrop High
150 mm²309 A241 A0.43 V (0.11%)399.6 V0.71 V (0.18%)262.1 WDrop High
185 mm²353 A275 A0.35 V (0.09%)399.6 V0.58 V (0.14%)212.6 W✓ OK (≤3%)
240 mm²415 A324 A0.27 V (0.07%)399.7 V0.45 V (0.11%)163.8 W✓ OK (≤3%)
300 mm²477 A372 A0.22 V (0.05%)399.8 V0.36 V (0.09%)131.1 W✓ OK (≤3%)
400 mm²570 A445 A0.16 V (0.04%)399.8 V0.27 V (0.07%)98.3 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 5 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 350A at 5 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 350A over 5m at 400V (voltage drop: 0.35V or 0.09%).

What is the power capacity of 350A at 400V?

At unity power factor, 350A at 400V supports 242.49 kW with a standard 350A circuit breaker.