⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

375 Amp Cable Size at 20 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 1.34V (0.58%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.32V (0.58%)
Voltage at Load228.7 VLine Loss: 501.6 W
Max Power & Breaker86.25 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A214.0 V (93.04%)16.0 V353.0 V (153.48%)80250.0 WDrop High
2.5 mm²24 A18 A128.4 V (55.83%)101.6 V211.8 V (92.09%)48150.0 WDrop High
4 mm²32 A25 A80.25 V (34.89%)149.8 V132.38 V (57.55%)30093.8 WDrop High
6 mm²41 A32 A53.5 V (23.26%)176.5 V88.25 V (38.37%)20062.5 WDrop High
10 mm²57 A44 A32.1 V (13.96%)197.9 V52.95 V (23.02%)12037.5 WDrop High
16 mm²76 A59 A20.06 V (8.72%)209.9 V33.09 V (14.39%)7523.4 WDrop High
25 mm²101 A78 A12.84 V (5.58%)217.2 V21.18 V (9.21%)4815.0 WDrop High
35 mm²125 A97 A9.17 V (3.99%)220.8 V15.13 V (6.58%)3439.3 WDrop High
50 mm²151 A118 A6.42 V (2.79%)223.6 V10.59 V (4.6%)2407.5 WDrop High
70 mm²192 A150 A4.59 V (1.99%)225.4 V7.56 V (3.29%)1719.6 WDrop High
95 mm²232 A181 A3.38 V (1.47%)226.6 V5.57 V (2.42%)1267.1 WDrop High
120 mm²269 A210 A2.68 V (1.16%)227.3 V4.41 V (1.92%)1003.1 WDrop High
150 mm²309 A241 A2.14 V (0.93%)227.9 V3.53 V (1.53%)802.5 WDrop High
185 mm²353 A275 A1.74 V (0.75%)228.3 V2.86 V (1.24%)650.7 WDrop High
240 mm²415 A324 A1.34 V (0.58%)228.7 V2.21 V (0.96%)501.6 W✓ OK (≤3%)
300 mm²477 A372 A1.07 V (0.47%)228.9 V1.76 V (0.77%)401.2 W✓ OK (≤3%)
400 mm²570 A445 A0.8 V (0.35%)229.2 V1.32 V (0.58%)300.9 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 20 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 375A at 20 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 20m at 230V (voltage drop: 1.34V or 0.58%).

What is the power capacity of 375A at 230V?

At unity power factor, 375A at 230V supports 86.25 kW with a standard 400A circuit breaker.