⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

375 Amp Cable Size at 70 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 4.68V (2.04%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.63V (2.01%)
Voltage at Load225.3 VLine Loss: 1755.5 W
Max Power & Breaker86.25 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A749.0 V (325.65%)0.0 V1235.5 V (537.17%)280875.0 WDrop High
2.5 mm²24 A18 A449.4 V (195.39%)0.0 V741.3 V (322.3%)168525.0 WDrop High
4 mm²32 A25 A280.88 V (122.12%)0.0 V463.31 V (201.44%)105328.1 WDrop High
6 mm²41 A32 A187.25 V (81.41%)42.8 V308.88 V (134.29%)70218.8 WDrop High
10 mm²57 A44 A112.35 V (48.85%)117.7 V185.33 V (80.58%)42131.2 WDrop High
16 mm²76 A59 A70.22 V (30.53%)159.8 V115.83 V (50.36%)26332.0 WDrop High
25 mm²101 A78 A44.94 V (19.54%)185.1 V74.13 V (32.23%)16852.5 WDrop High
35 mm²125 A97 A32.1 V (13.96%)197.9 V52.95 V (23.02%)12037.5 WDrop High
50 mm²151 A118 A22.47 V (9.77%)207.5 V37.06 V (16.12%)8426.2 WDrop High
70 mm²192 A150 A16.05 V (6.98%)213.9 V26.47 V (11.51%)6018.8 WDrop High
95 mm²232 A181 A11.83 V (5.14%)218.2 V19.51 V (8.48%)4434.9 WDrop High
120 mm²269 A210 A9.36 V (4.07%)220.6 V15.44 V (6.71%)3510.9 WDrop High
150 mm²309 A241 A7.49 V (3.26%)222.5 V12.36 V (5.37%)2808.8 WDrop High
185 mm²353 A275 A6.07 V (2.64%)223.9 V10.02 V (4.36%)2277.4 WDrop High
240 mm²415 A324 A4.68 V (2.04%)225.3 V7.72 V (3.36%)1755.5 W✓ OK (≤3%)
300 mm²477 A372 A3.74 V (1.63%)226.3 V6.18 V (2.69%)1404.4 W✓ OK (≤3%)
400 mm²570 A445 A2.81 V (1.22%)227.2 V4.63 V (2.01%)1053.3 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 70 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 375A at 70 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 70m at 230V (voltage drop: 4.68V or 2.04%).

What is the power capacity of 375A at 230V?

At unity power factor, 375A at 230V supports 86.25 kW with a standard 400A circuit breaker.