375 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 2.03V (0.29%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.01V (0.29%)
Voltage at Load688.0 VLine Loss: 1316.6 W
Max Power & Breaker448.17 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A324.33 V (47.0%)365.7 V534.99 V (77.53%)210656.2 WDrop High
2.5 mm²24 A18 A194.6 V (28.2%)495.4 V320.99 V (46.52%)126393.7 WDrop High
4 mm²32 A25 A121.62 V (17.63%)568.4 V200.62 V (29.08%)78996.1 WDrop High
6 mm²41 A32 A81.08 V (11.75%)608.9 V133.75 V (19.38%)52664.1 WDrop High
10 mm²57 A44 A48.65 V (7.05%)641.4 V80.25 V (11.63%)31598.4 WDrop High
16 mm²76 A59 A30.41 V (4.41%)659.6 V50.16 V (7.27%)19749.0 WDrop High
25 mm²101 A78 A19.46 V (2.82%)670.5 V32.1 V (4.65%)12639.4 WDrop High
35 mm²125 A97 A13.9 V (2.01%)676.1 V22.93 V (3.32%)9028.1 WDrop High
50 mm²151 A118 A9.73 V (1.41%)680.3 V16.05 V (2.33%)6319.7 WDrop High
70 mm²192 A150 A6.95 V (1.01%)683.1 V11.46 V (1.66%)4514.1 WDrop High
95 mm²232 A181 A5.12 V (0.74%)684.9 V8.45 V (1.22%)3326.2 WDrop High
120 mm²269 A210 A4.05 V (0.59%)685.9 V6.69 V (0.97%)2633.2 WDrop High
150 mm²309 A241 A3.24 V (0.47%)686.8 V5.35 V (0.78%)2106.6 WDrop High
185 mm²353 A275 A2.63 V (0.38%)687.4 V4.34 V (0.63%)1708.0 WDrop High
240 mm²415 A324 A2.03 V (0.29%)688.0 V3.34 V (0.48%)1316.6 W✓ OK (≤3%)
300 mm²477 A372 A1.62 V (0.24%)688.4 V2.67 V (0.39%)1053.3 W✓ OK (≤3%)
400 mm²570 A445 A1.22 V (0.18%)688.8 V2.01 V (0.29%)790.0 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 375A at 35 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 35m at 690V (voltage drop: 2.03V or 0.29%).

What is the power capacity of 375A at 690V?

At unity power factor, 375A at 690V supports 448.17 kW with a standard 400A circuit breaker.