375 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 1.45V (0.21%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.43V (0.21%)
Voltage at Load688.6 VLine Loss: 940.4 W
Max Power & Breaker448.17 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A231.66 V (33.57%)458.3 V382.13 V (55.38%)150468.7 WDrop High
2.5 mm²24 A18 A139.0 V (20.14%)551.0 V229.28 V (33.23%)90281.2 WDrop High
4 mm²32 A25 A86.87 V (12.59%)603.1 V143.3 V (20.77%)56425.8 WDrop High
6 mm²41 A32 A57.92 V (8.39%)632.1 V95.53 V (13.85%)37617.2 WDrop High
10 mm²57 A44 A34.75 V (5.04%)655.3 V57.32 V (8.31%)22570.3 WDrop High
16 mm²76 A59 A21.72 V (3.15%)668.3 V35.83 V (5.19%)14106.4 WDrop High
25 mm²101 A78 A13.9 V (2.01%)676.1 V22.93 V (3.32%)9028.1 WDrop High
35 mm²125 A97 A9.93 V (1.44%)680.1 V16.38 V (2.37%)6448.7 WDrop High
50 mm²151 A118 A6.95 V (1.01%)683.1 V11.46 V (1.66%)4514.1 WDrop High
70 mm²192 A150 A4.96 V (0.72%)685.0 V8.19 V (1.19%)3224.3 WDrop High
95 mm²232 A181 A3.66 V (0.53%)686.3 V6.03 V (0.87%)2375.8 WDrop High
120 mm²269 A210 A2.9 V (0.42%)687.1 V4.78 V (0.69%)1880.9 WDrop High
150 mm²309 A241 A2.32 V (0.34%)687.7 V3.82 V (0.55%)1504.7 WDrop High
185 mm²353 A275 A1.88 V (0.27%)688.1 V3.1 V (0.45%)1220.0 WDrop High
240 mm²415 A324 A1.45 V (0.21%)688.6 V2.39 V (0.35%)940.4 W✓ OK (≤3%)
300 mm²477 A372 A1.16 V (0.17%)688.8 V1.91 V (0.28%)752.3 W✓ OK (≤3%)
400 mm²570 A445 A0.87 V (0.13%)689.1 V1.43 V (0.21%)564.3 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 375A at 25 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 25m at 690V (voltage drop: 1.45V or 0.21%).

What is the power capacity of 375A at 690V?

At unity power factor, 375A at 690V supports 448.17 kW with a standard 400A circuit breaker.