375 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 0.33V (1.39%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.33V (1.38%)
Voltage at Load23.7 VLine Loss: 125.4 W
Max Power & Breaker9.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A53.5 V (222.92%)0.0 V88.25 V (367.71%)20062.5 WDrop High
2.5 mm²24 A18 A32.1 V (133.75%)0.0 V52.95 V (220.62%)12037.5 WDrop High
4 mm²32 A25 A20.06 V (83.59%)3.9 V33.09 V (137.89%)7523.4 WDrop High
6 mm²41 A32 A13.38 V (55.73%)10.6 V22.06 V (91.93%)5015.6 WDrop High
10 mm²57 A44 A8.03 V (33.44%)16.0 V13.24 V (55.16%)3009.4 WDrop High
16 mm²76 A59 A5.02 V (20.9%)19.0 V8.27 V (34.47%)1880.9 WDrop High
25 mm²101 A78 A3.21 V (13.38%)20.8 V5.29 V (22.06%)1203.8 WDrop High
35 mm²125 A97 A2.29 V (9.55%)21.7 V3.78 V (15.76%)859.8 WDrop High
50 mm²151 A118 A1.6 V (6.69%)22.4 V2.65 V (11.03%)601.9 WDrop High
70 mm²192 A150 A1.15 V (4.78%)22.9 V1.89 V (7.88%)429.9 WDrop High
95 mm²232 A181 A0.84 V (3.52%)23.2 V1.39 V (5.81%)316.8 WDrop High
120 mm²269 A210 A0.67 V (2.79%)23.3 V1.1 V (4.6%)250.8 WDrop High
150 mm²309 A241 A0.53 V (2.23%)23.5 V0.88 V (3.68%)200.6 WDrop High
185 mm²353 A275 A0.43 V (1.81%)23.6 V0.72 V (2.98%)162.7 WDrop High
240 mm²415 A324 A0.33 V (1.39%)23.7 V0.55 V (2.3%)125.4 W✓ OK (≤3%)
300 mm²477 A372 A0.27 V (1.11%)23.7 V0.44 V (1.84%)100.3 W✓ OK (≤3%)
400 mm²570 A445 A0.2 V (0.84%)23.8 V0.33 V (1.38%)75.2 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 375A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 375A over 5m at 24V (voltage drop: 0.33V or 1.39%).

What is the power capacity of 375A at 24V?

At unity power factor, 375A at 24V supports 9.0 kW with a standard 400A circuit breaker.