375 Amp Cable Size at 500 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.69V (2.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 28.66V (7.17%)
Voltage at Load391.3 VLine Loss: 5642.6 W
Max Power & Breaker259.81 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4633.24 V (1158.31%)0.0 V7642.67 V (1910.67%)3009375.0 WDrop High
2.5 mm²24 A18 A2779.94 V (694.99%)0.0 V4585.6 V (1146.4%)1805625.0 WDrop High
4 mm²32 A25 A1737.46 V (434.37%)0.0 V2866.0 V (716.5%)1128515.6 WDrop High
6 mm²41 A32 A1158.31 V (289.58%)0.0 V1910.67 V (477.67%)752343.8 WDrop High
10 mm²57 A44 A694.99 V (173.75%)0.0 V1146.4 V (286.6%)451406.2 WDrop High
16 mm²76 A59 A434.37 V (108.59%)0.0 V716.5 V (179.13%)282128.9 WDrop High
25 mm²101 A78 A277.99 V (69.5%)122.0 V458.56 V (114.64%)180562.5 WDrop High
35 mm²125 A97 A198.57 V (49.64%)201.4 V327.54 V (81.89%)128973.2 WDrop High
50 mm²151 A118 A139.0 V (34.75%)261.0 V229.28 V (57.32%)90281.2 WDrop High
70 mm²192 A150 A99.28 V (24.82%)300.7 V163.77 V (40.94%)64486.6 WDrop High
95 mm²232 A181 A73.16 V (18.29%)326.8 V120.67 V (30.17%)47516.4 WDrop High
120 mm²269 A210 A57.92 V (14.48%)342.1 V95.53 V (23.88%)37617.2 WDrop High
150 mm²309 A241 A46.33 V (11.58%)353.7 V76.43 V (19.11%)30093.8 WDrop High
185 mm²353 A275 A37.57 V (9.39%)362.4 V61.97 V (15.49%)24400.3 WDrop High
240 mm²415 A324 A28.96 V (7.24%)371.0 V47.77 V (11.94%)18808.6 WDrop High
300 mm²477 A372 A23.17 V (5.79%)376.8 V38.21 V (9.55%)15046.9 WDrop High
400 mm²570 A445 A17.37 V (4.34%)382.6 V28.66 V (7.17%)11285.2 W~ ≤5%

FAQ — 375 Amp Cable Size at 500 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 375A at 500 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 375A over 500m at 400V (voltage drop: 8.69V or 2.17%).

What is the power capacity of 375A at 400V?

At unity power factor, 375A at 400V supports 259.81 kW with a standard 400A circuit breaker.