40 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.68V (2.85%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.85V (3.53%)
Voltage at Load23.3 VLine Loss: 27.4 W
Max Power & Breaker0.96 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A136.96 V (570.67%)0.0 V225.92 V (941.33%)5478.4 WDrop High
2.5 mm²24 A18 A82.18 V (342.4%)0.0 V135.55 V (564.8%)3287.0 WDrop High
4 mm²32 A25 A51.36 V (214.0%)0.0 V84.72 V (353.0%)2054.4 WDrop High
6 mm²41 A32 A34.24 V (142.67%)0.0 V56.48 V (235.33%)1369.6 WDrop High
10 mm²57 A44 A20.54 V (85.6%)3.5 V33.89 V (141.2%)821.8 WDrop High
16 mm²76 A59 A12.84 V (53.5%)11.2 V21.18 V (88.25%)513.6 WDrop High
25 mm²101 A78 A8.22 V (34.24%)15.8 V13.56 V (56.48%)328.7 WDrop High
35 mm²125 A97 A5.87 V (24.46%)18.1 V9.68 V (40.34%)234.8 WDrop High
50 mm²151 A118 A4.11 V (17.12%)19.9 V6.78 V (28.24%)164.4 WDrop High
70 mm²192 A150 A2.93 V (12.23%)21.1 V4.84 V (20.17%)117.4 WDrop High
95 mm²232 A181 A2.16 V (9.01%)21.8 V3.57 V (14.86%)86.5 WDrop High
120 mm²269 A210 A1.71 V (7.13%)22.3 V2.82 V (11.77%)68.5 WDrop High
150 mm²309 A241 A1.37 V (5.71%)22.6 V2.26 V (9.41%)54.8 WDrop High
185 mm²353 A275 A1.11 V (4.63%)22.9 V1.83 V (7.63%)44.4 W~ ≤5%
240 mm²415 A324 A0.86 V (3.57%)23.1 V1.41 V (5.88%)34.2 W~ ≤5%
300 mm²477 A372 A0.68 V (2.85%)23.3 V1.13 V (4.71%)27.4 W✓ OK (≤3%)
400 mm²570 A445 A0.51 V (2.14%)23.5 V0.85 V (3.53%)20.5 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 40A at 120 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 40A over 120m at 24V (voltage drop: 0.68V or 2.85%).

What is the power capacity of 40A at 24V?

At unity power factor, 40A at 24V supports 0.96 kW with a standard 40A circuit breaker.