20 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 0.68V (2.85%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.71V (2.94%)
Voltage at Load23.3 VLine Loss: 13.7 W
Max Power & Breaker0.48 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A68.48 V (285.33%)0.0 V112.96 V (470.67%)1369.6 WDrop High
2.5 mm²24 A18 A41.09 V (171.2%)0.0 V67.78 V (282.4%)821.8 WDrop High
4 mm²32 A25 A25.68 V (107.0%)0.0 V42.36 V (176.5%)513.6 WDrop High
6 mm²41 A32 A17.12 V (71.33%)6.9 V28.24 V (117.67%)342.4 WDrop High
10 mm²57 A44 A10.27 V (42.8%)13.7 V16.94 V (70.6%)205.4 WDrop High
16 mm²76 A59 A6.42 V (26.75%)17.6 V10.59 V (44.12%)128.4 WDrop High
25 mm²101 A78 A4.11 V (17.12%)19.9 V6.78 V (28.24%)82.2 WDrop High
35 mm²125 A97 A2.93 V (12.23%)21.1 V4.84 V (20.17%)58.7 WDrop High
50 mm²151 A118 A2.05 V (8.56%)21.9 V3.39 V (14.12%)41.1 WDrop High
70 mm²192 A150 A1.47 V (6.11%)22.5 V2.42 V (10.09%)29.3 WDrop High
95 mm²232 A181 A1.08 V (4.51%)22.9 V1.78 V (7.43%)21.6 W~ ≤5%
120 mm²269 A210 A0.86 V (3.57%)23.1 V1.41 V (5.88%)17.1 W~ ≤5%
150 mm²309 A241 A0.68 V (2.85%)23.3 V1.13 V (4.71%)13.7 W✓ OK (≤3%)
185 mm²353 A275 A0.56 V (2.31%)23.4 V0.92 V (3.82%)11.1 W✓ OK (≤3%)
240 mm²415 A324 A0.43 V (1.78%)23.6 V0.71 V (2.94%)8.6 W✓ OK (≤3%)
300 mm²477 A372 A0.34 V (1.43%)23.7 V0.56 V (2.35%)6.8 W✓ OK (≤3%)
400 mm²570 A445 A0.26 V (1.07%)23.7 V0.42 V (1.76%)5.1 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 20A at 120 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 20A over 120m at 24V (voltage drop: 0.68V or 2.85%).

What is the power capacity of 20A at 24V?

At unity power factor, 20A at 24V supports 0.48 kW with a standard 20A circuit breaker.