⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

40 Amp Cable Size at 250 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 10.59V (2.65%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 8.73V (2.18%)
Voltage at Load389.4 VLine Loss: 733.7 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A247.11 V (61.78%)152.9 V407.61 V (101.9%)17120.0 WDrop High
2.5 mm²24 A18 A148.26 V (37.07%)251.7 V244.57 V (61.14%)10272.0 WDrop High
4 mm²32 A25 A92.66 V (23.17%)307.3 V152.85 V (38.21%)6420.0 WDrop High
6 mm²41 A32 A61.78 V (15.44%)338.2 V101.9 V (25.48%)4280.0 WDrop High
10 mm²57 A44 A37.07 V (9.27%)362.9 V61.14 V (15.29%)2568.0 WDrop High
16 mm²76 A59 A23.17 V (5.79%)376.8 V38.21 V (9.55%)1605.0 WDrop High
25 mm²101 A78 A14.83 V (3.71%)385.2 V24.46 V (6.11%)1027.2 W~ ≤5%
35 mm²125 A97 A10.59 V (2.65%)389.4 V17.47 V (4.37%)733.7 W✓ OK (≤3%)
50 mm²151 A118 A7.41 V (1.85%)392.6 V12.23 V (3.06%)513.6 W✓ OK (≤3%)
70 mm²192 A150 A5.3 V (1.32%)394.7 V8.73 V (2.18%)366.9 W✓ OK (≤3%)
95 mm²232 A181 A3.9 V (0.98%)396.1 V6.44 V (1.61%)270.3 W✓ OK (≤3%)
120 mm²269 A210 A3.09 V (0.77%)396.9 V5.1 V (1.27%)214.0 W✓ OK (≤3%)
150 mm²309 A241 A2.47 V (0.62%)397.5 V4.08 V (1.02%)171.2 W✓ OK (≤3%)
185 mm²353 A275 A2.0 V (0.5%)398.0 V3.3 V (0.83%)138.8 W✓ OK (≤3%)
240 mm²415 A324 A1.54 V (0.39%)398.5 V2.55 V (0.64%)107.0 W✓ OK (≤3%)
300 mm²477 A372 A1.24 V (0.31%)398.8 V2.04 V (0.51%)85.6 W✓ OK (≤3%)
400 mm²570 A445 A0.93 V (0.23%)399.1 V1.53 V (0.38%)64.2 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 250 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 40A at 250 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 40A over 250m at 400V (voltage drop: 10.59V or 2.65%).

What is the power capacity of 40A at 400V?

At unity power factor, 40A at 400V supports 27.71 kW with a standard 40A circuit breaker.