40 Amp Cable Size at 35 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 40 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 8.65V (2.08%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 8.56V (2.06%)
Voltage at Load406.4 VLine Loss: 599.2 W
Max Power & Breaker28.75 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A34.59 V (8.34%)380.4 V57.07 V (13.75%)2396.8 WDrop High
2.5 mm²24 A18 A20.76 V (5.0%)394.2 V34.24 V (8.25%)1438.1 WDrop High
4 mm²32 A25 A12.97 V (3.13%)402.0 V21.4 V (5.16%)898.8 WDrop High
6 mm²41 A32 A8.65 V (2.08%)406.4 V14.27 V (3.44%)599.2 W✓ OK (≤3%)
10 mm²57 A44 A5.19 V (1.25%)409.8 V8.56 V (2.06%)359.5 W✓ OK (≤3%)
16 mm²76 A59 A3.24 V (0.78%)411.8 V5.35 V (1.29%)224.7 W✓ OK (≤3%)
25 mm²101 A78 A2.08 V (0.5%)412.9 V3.42 V (0.83%)143.8 W✓ OK (≤3%)
35 mm²125 A97 A1.48 V (0.36%)413.5 V2.45 V (0.59%)102.7 W✓ OK (≤3%)
50 mm²151 A118 A1.04 V (0.25%)414.0 V1.71 V (0.41%)71.9 W✓ OK (≤3%)
70 mm²192 A150 A0.74 V (0.18%)414.3 V1.22 V (0.29%)51.4 W✓ OK (≤3%)
95 mm²232 A181 A0.55 V (0.13%)414.5 V0.9 V (0.22%)37.8 W✓ OK (≤3%)
120 mm²269 A210 A0.43 V (0.1%)414.6 V0.71 V (0.17%)30.0 W✓ OK (≤3%)
150 mm²309 A241 A0.35 V (0.08%)414.7 V0.57 V (0.14%)24.0 W✓ OK (≤3%)
185 mm²353 A275 A0.28 V (0.07%)414.7 V0.46 V (0.11%)19.4 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.05%)414.8 V0.36 V (0.09%)15.0 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.04%)414.8 V0.29 V (0.07%)12.0 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.03%)414.9 V0.21 V (0.05%)9.0 W✓ OK (≤3%)

FAQ — 40 Amp Cable Size at 35 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 40A at 35 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 40A over 35m at 415V (voltage drop: 8.65V or 2.08%).

What is the power capacity of 40A at 415V?

At unity power factor, 40A at 415V supports 28.75 kW with a standard 40A circuit breaker.