⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

400 Amp Cable Size at 60 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 4.28V (1.86%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.24V (1.84%)
Voltage at Load225.7 VLine Loss: 1712.0 W
Max Power & Breaker92.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A684.8 V (297.74%)0.0 V1129.6 V (491.13%)273920.0 WDrop High
2.5 mm²24 A18 A410.88 V (178.64%)0.0 V677.76 V (294.68%)164352.0 WDrop High
4 mm²32 A25 A256.8 V (111.65%)0.0 V423.6 V (184.17%)102720.0 WDrop High
6 mm²41 A32 A171.2 V (74.43%)58.8 V282.4 V (122.78%)68480.0 WDrop High
10 mm²57 A44 A102.72 V (44.66%)127.3 V169.44 V (73.67%)41088.0 WDrop High
16 mm²76 A59 A64.2 V (27.91%)165.8 V105.9 V (46.04%)25680.0 WDrop High
25 mm²101 A78 A41.09 V (17.86%)188.9 V67.78 V (29.47%)16435.2 WDrop High
35 mm²125 A97 A29.35 V (12.76%)200.7 V48.41 V (21.05%)11739.4 WDrop High
50 mm²151 A118 A20.54 V (8.93%)209.5 V33.89 V (14.73%)8217.6 WDrop High
70 mm²192 A150 A14.67 V (6.38%)215.3 V24.21 V (10.52%)5869.7 WDrop High
95 mm²232 A181 A10.81 V (4.7%)219.2 V17.84 V (7.75%)4325.1 WDrop High
120 mm²269 A210 A8.56 V (3.72%)221.4 V14.12 V (6.14%)3424.0 WDrop High
150 mm²309 A241 A6.85 V (2.98%)223.2 V11.3 V (4.91%)2739.2 WDrop High
185 mm²353 A275 A5.55 V (2.41%)224.4 V9.16 V (3.98%)2221.0 WDrop High
240 mm²415 A324 A4.28 V (1.86%)225.7 V7.06 V (3.07%)1712.0 W✓ OK (≤3%)
300 mm²477 A372 A3.42 V (1.49%)226.6 V5.65 V (2.46%)1369.6 W✓ OK (≤3%)
400 mm²570 A445 A2.57 V (1.12%)227.4 V4.24 V (1.84%)1027.2 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 60 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 400A at 60 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 60m at 230V (voltage drop: 4.28V or 1.86%).

What is the power capacity of 400A at 230V?

At unity power factor, 400A at 230V supports 92.0 kW with a standard 400A circuit breaker.