⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

32 Amp Cable Size at 60 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 5.42V (2.36%)
Voltage at Load224.9 VLine Loss: 164.4 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A54.78 V (23.82%)175.2 V90.37 V (39.29%)1753.1 WDrop High
2.5 mm²24 A18 A32.87 V (14.29%)197.1 V54.22 V (23.57%)1051.9 WDrop High
4 mm²32 A25 A20.54 V (8.93%)209.5 V33.89 V (14.73%)657.4 WDrop High
6 mm²41 A32 A13.7 V (5.95%)216.3 V22.59 V (9.82%)438.3 WDrop High
10 mm²57 A44 A8.22 V (3.57%)221.8 V13.56 V (5.89%)263.0 W~ ≤5%
16 mm²76 A59 A5.14 V (2.23%)224.9 V8.47 V (3.68%)164.4 W✓ OK (≤3%)
25 mm²101 A78 A3.29 V (1.43%)226.7 V5.42 V (2.36%)105.2 W✓ OK (≤3%)
35 mm²125 A97 A2.35 V (1.02%)227.7 V3.87 V (1.68%)75.1 W✓ OK (≤3%)
50 mm²151 A118 A1.64 V (0.71%)228.4 V2.71 V (1.18%)52.6 W✓ OK (≤3%)
70 mm²192 A150 A1.17 V (0.51%)228.8 V1.94 V (0.84%)37.6 W✓ OK (≤3%)
95 mm²232 A181 A0.87 V (0.38%)229.1 V1.43 V (0.62%)27.7 W✓ OK (≤3%)
120 mm²269 A210 A0.68 V (0.3%)229.3 V1.13 V (0.49%)21.9 W✓ OK (≤3%)
150 mm²309 A241 A0.55 V (0.24%)229.5 V0.9 V (0.39%)17.5 W✓ OK (≤3%)
185 mm²353 A275 A0.44 V (0.19%)229.6 V0.73 V (0.32%)14.2 W✓ OK (≤3%)
240 mm²415 A324 A0.34 V (0.15%)229.7 V0.56 V (0.25%)11.0 W✓ OK (≤3%)
300 mm²477 A372 A0.27 V (0.12%)229.7 V0.45 V (0.2%)8.8 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.09%)229.8 V0.34 V (0.15%)6.6 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 60 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 32A at 60 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 32A over 60m at 230V (voltage drop: 5.14V or 2.23%).

What is the power capacity of 32A at 230V?

At unity power factor, 32A at 230V supports 7.36 kW with a standard 32A circuit breaker.