400 Amp Cable Size at 600 Meters (400V Three-Phase (IEC European Grid))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 600 m (1968.5 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 36.68V (9.17%)
Voltage at Load388.9 VLine Loss: 7704.0 W
Max Power & Breaker277.13 kW400A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 5930.54 V (1482.64%) | 0.0 V | 9782.62 V (2445.66%) | 4108800.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 3558.33 V (889.58%) | 0.0 V | 5869.57 V (1467.39%) | 2465280.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 2223.95 V (555.99%) | 0.0 V | 3668.48 V (917.12%) | 1540800.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 1482.64 V (370.66%) | 0.0 V | 2445.66 V (611.41%) | 1027200.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 889.58 V (222.4%) | 0.0 V | 1467.39 V (366.85%) | 616320.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 555.99 V (139.0%) | 0.0 V | 917.12 V (229.28%) | 385200.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 355.83 V (88.96%) | 44.2 V | 586.96 V (146.74%) | 246528.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 254.17 V (63.54%) | 145.8 V | 419.26 V (104.81%) | 176091.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 177.92 V (44.48%) | 222.1 V | 293.48 V (73.37%) | 123264.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 127.08 V (31.77%) | 272.9 V | 209.63 V (52.41%) | 88045.7 W | Drop High |
| 95 mm² | 232 A | 181 A | 93.64 V (23.41%) | 306.4 V | 154.46 V (38.62%) | 64875.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 74.13 V (18.53%) | 325.9 V | 122.28 V (30.57%) | 51360.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 59.31 V (14.83%) | 340.7 V | 97.83 V (24.46%) | 41088.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 48.09 V (12.02%) | 351.9 V | 79.32 V (19.83%) | 33314.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 37.07 V (9.27%) | 362.9 V | 61.14 V (15.29%) | 25680.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 29.65 V (7.41%) | 370.3 V | 48.91 V (12.23%) | 20544.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 22.24 V (5.56%) | 377.8 V | 36.68 V (9.17%) | 15408.0 W | Drop High |
FAQ — 400 Amp Cable Size at 600 Meters (400V Three-Phase (IEC European Grid))
What mm² cable size is required for 400A at 600 meters (400V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 400A over 600m at 400V (voltage drop: 11.12V or 2.78%).
What is the power capacity of 400A at 400V?
At unity power factor, 400A at 400V supports 277.13 kW with a standard 400A circuit breaker.
Related Lengths & Currents (400V)
400A · 5m (400V)400A · 10m (400V)400A · 15m (400V)400A · 20m (400V)400A · 25m (400V)400A · 30m (400V)400A · 35m (400V)400A · 40m (400V)400A · 45m (400V)400A · 50m (400V)400A · 60m (400V)400A · 70m (400V)10A · 600m (400V)16A · 600m (400V)20A · 600m (400V)25A · 600m (400V)32A · 600m (400V)40A · 600m (400V)50A · 600m (400V)63A · 600m (400V)80A · 600m (400V)100A · 600m (400V)125A · 600m (400V)160A · 600m (400V)200A · 600m (400V)