400 Amp Cable Size at 80 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 4.94V (1.24%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.89V (1.22%)
Voltage at Load395.1 VLine Loss: 3424.0 W
Max Power & Breaker277.13 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A790.74 V (197.68%)0.0 V1304.35 V (326.09%)547840.0 WDrop High
2.5 mm²24 A18 A474.44 V (118.61%)0.0 V782.61 V (195.65%)328704.0 WDrop High
4 mm²32 A25 A296.53 V (74.13%)103.5 V489.13 V (122.28%)205440.0 WDrop High
6 mm²41 A32 A197.68 V (49.42%)202.3 V326.09 V (81.52%)136960.0 WDrop High
10 mm²57 A44 A118.61 V (29.65%)281.4 V195.65 V (48.91%)82176.0 WDrop High
16 mm²76 A59 A74.13 V (18.53%)325.9 V122.28 V (30.57%)51360.0 WDrop High
25 mm²101 A78 A47.44 V (11.86%)352.6 V78.26 V (19.57%)32870.4 WDrop High
35 mm²125 A97 A33.89 V (8.47%)366.1 V55.9 V (13.98%)23478.9 WDrop High
50 mm²151 A118 A23.72 V (5.93%)376.3 V39.13 V (9.78%)16435.2 WDrop High
70 mm²192 A150 A16.94 V (4.24%)383.1 V27.95 V (6.99%)11739.4 WDrop High
95 mm²232 A181 A12.49 V (3.12%)387.5 V20.59 V (5.15%)8650.1 WDrop High
120 mm²269 A210 A9.88 V (2.47%)390.1 V16.3 V (4.08%)6848.0 WDrop High
150 mm²309 A241 A7.91 V (1.98%)392.1 V13.04 V (3.26%)5478.4 WDrop High
185 mm²353 A275 A6.41 V (1.6%)393.6 V10.58 V (2.64%)4441.9 WDrop High
240 mm²415 A324 A4.94 V (1.24%)395.1 V8.15 V (2.04%)3424.0 W✓ OK (≤3%)
300 mm²477 A372 A3.95 V (0.99%)396.0 V6.52 V (1.63%)2739.2 W✓ OK (≤3%)
400 mm²570 A445 A2.97 V (0.74%)397.0 V4.89 V (1.22%)2054.4 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 80 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 400A at 80 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 80m at 400V (voltage drop: 4.94V or 1.24%).

What is the power capacity of 400A at 400V?

At unity power factor, 400A at 400V supports 277.13 kW with a standard 400A circuit breaker.