450 Amp Cable Size at 120 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 6.67V (1.67%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.25V (2.06%)
Voltage at Load393.3 VLine Loss: 5200.2 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1334.37 V (333.59%)0.0 V2201.09 V (550.27%)1040040.0 WDrop High
2.5 mm²24 A18 A800.62 V (200.16%)0.0 V1320.65 V (330.16%)624024.0 WDrop High
4 mm²32 A25 A500.39 V (125.1%)0.0 V825.41 V (206.35%)390015.0 WDrop High
6 mm²41 A32 A333.59 V (83.4%)66.4 V550.27 V (137.57%)260010.0 WDrop High
10 mm²57 A44 A200.16 V (50.04%)199.8 V330.16 V (82.54%)156006.0 WDrop High
16 mm²76 A59 A125.1 V (31.27%)274.9 V206.35 V (51.59%)97503.8 WDrop High
25 mm²101 A78 A80.06 V (20.02%)319.9 V132.07 V (33.02%)62402.4 WDrop High
35 mm²125 A97 A57.19 V (14.3%)342.8 V94.33 V (23.58%)44573.1 WDrop High
50 mm²151 A118 A40.03 V (10.01%)360.0 V66.03 V (16.51%)31201.2 WDrop High
70 mm²192 A150 A28.59 V (7.15%)371.4 V47.17 V (11.79%)22286.6 WDrop High
95 mm²232 A181 A21.07 V (5.27%)378.9 V34.75 V (8.69%)16421.7 WDrop High
120 mm²269 A210 A16.68 V (4.17%)383.3 V27.51 V (6.88%)13000.5 WDrop High
150 mm²309 A241 A13.34 V (3.34%)386.7 V22.01 V (5.5%)10400.4 WDrop High
185 mm²353 A275 A10.82 V (2.7%)389.2 V17.85 V (4.46%)8432.8 WDrop High
240 mm²415 A324 A8.34 V (2.08%)391.7 V13.76 V (3.44%)6500.2 WDrop High
300 mm²477 A372 A6.67 V (1.67%)393.3 V11.01 V (2.75%)5200.2 W✓ OK (≤3%)
400 mm²570 A445 A5.0 V (1.25%)395.0 V8.25 V (2.06%)3900.2 W✓ OK (≤3%)

FAQ — 450 Amp Cable Size at 120 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 450A at 120 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 120m at 400V (voltage drop: 6.67V or 1.67%).

What is the power capacity of 450A at 400V?

At unity power factor, 450A at 400V supports 311.77 kW with a standard 450A circuit breaker.