450 Amp Cable Size at 300 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.25V (1.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 20.64V (5.16%)
Voltage at Load393.8 VLine Loss: 4875.2 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3335.93 V (833.98%)0.0 V5502.73 V (1375.68%)2600100.0 WDrop High
2.5 mm²24 A18 A2001.56 V (500.39%)0.0 V3301.64 V (825.41%)1560060.0 WDrop High
4 mm²32 A25 A1250.97 V (312.74%)0.0 V2063.52 V (515.88%)975037.5 WDrop High
6 mm²41 A32 A833.98 V (208.5%)0.0 V1375.68 V (343.92%)650025.0 WDrop High
10 mm²57 A44 A500.39 V (125.1%)0.0 V825.41 V (206.35%)390015.0 WDrop High
16 mm²76 A59 A312.74 V (78.19%)87.3 V515.88 V (128.97%)243759.4 WDrop High
25 mm²101 A78 A200.16 V (50.04%)199.8 V330.16 V (82.54%)156006.0 WDrop High
35 mm²125 A97 A142.97 V (35.74%)257.0 V235.83 V (58.96%)111432.9 WDrop High
50 mm²151 A118 A100.08 V (25.02%)299.9 V165.08 V (41.27%)78003.0 WDrop High
70 mm²192 A150 A71.48 V (17.87%)328.5 V117.92 V (29.48%)55716.4 WDrop High
95 mm²232 A181 A52.67 V (13.17%)347.3 V86.89 V (21.72%)41054.2 WDrop High
120 mm²269 A210 A41.7 V (10.42%)358.3 V68.78 V (17.2%)32501.2 WDrop High
150 mm²309 A241 A33.36 V (8.34%)366.6 V55.03 V (13.76%)26001.0 WDrop High
185 mm²353 A275 A27.05 V (6.76%)373.0 V44.62 V (11.15%)21081.9 WDrop High
240 mm²415 A324 A20.85 V (5.21%)379.2 V34.39 V (8.6%)16250.6 WDrop High
300 mm²477 A372 A16.68 V (4.17%)383.3 V27.51 V (6.88%)13000.5 W~ ≤5%
400 mm²570 A445 A12.51 V (3.13%)387.5 V20.64 V (5.16%)9750.4 W~ ≤5%

FAQ — 450 Amp Cable Size at 300 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 450A at 300 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 450A over 300m at 400V (voltage drop: 6.25V or 1.56%).

What is the power capacity of 450A at 400V?

At unity power factor, 450A at 400V supports 311.77 kW with a standard 450A circuit breaker.