450 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.32V (0.67%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.4V (0.83%)
Voltage at Load47.7 VLine Loss: 144.4 W
Max Power & Breaker21.6 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A64.2 V (133.75%)0.0 V105.9 V (220.62%)28890.0 WDrop High
2.5 mm²24 A18 A38.52 V (80.25%)9.5 V63.54 V (132.38%)17334.0 WDrop High
4 mm²32 A25 A24.07 V (50.16%)23.9 V39.71 V (82.73%)10833.8 WDrop High
6 mm²41 A32 A16.05 V (33.44%)31.9 V26.47 V (55.16%)7222.5 WDrop High
10 mm²57 A44 A9.63 V (20.06%)38.4 V15.88 V (33.09%)4333.5 WDrop High
16 mm²76 A59 A6.02 V (12.54%)42.0 V9.93 V (20.68%)2708.4 WDrop High
25 mm²101 A78 A3.85 V (8.03%)44.1 V6.35 V (13.24%)1733.4 WDrop High
35 mm²125 A97 A2.75 V (5.73%)45.2 V4.54 V (9.46%)1238.1 WDrop High
50 mm²151 A118 A1.93 V (4.01%)46.1 V3.18 V (6.62%)866.7 WDrop High
70 mm²192 A150 A1.38 V (2.87%)46.6 V2.27 V (4.73%)619.1 WDrop High
95 mm²232 A181 A1.01 V (2.11%)47.0 V1.67 V (3.48%)456.2 WDrop High
120 mm²269 A210 A0.8 V (1.67%)47.2 V1.32 V (2.76%)361.1 WDrop High
150 mm²309 A241 A0.64 V (1.34%)47.4 V1.06 V (2.21%)288.9 WDrop High
185 mm²353 A275 A0.52 V (1.08%)47.5 V0.86 V (1.79%)234.2 WDrop High
240 mm²415 A324 A0.4 V (0.84%)47.6 V0.66 V (1.38%)180.6 WDrop High
300 mm²477 A372 A0.32 V (0.67%)47.7 V0.53 V (1.1%)144.4 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (0.5%)47.8 V0.4 V (0.83%)108.3 W✓ OK (≤3%)

FAQ — 450 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 450A at 5 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 5m at 48V (voltage drop: 0.32V or 0.67%).

What is the power capacity of 450A at 48V?

At unity power factor, 450A at 48V supports 21.6 kW with a standard 450A circuit breaker.