450 Amp Cable Size at 500 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 10.43V (2.6%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 34.39V (8.6%)
Voltage at Load389.6 VLine Loss: 8125.3 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5559.88 V (1389.97%)0.0 V9171.21 V (2292.8%)4333500.0 WDrop High
2.5 mm²24 A18 A3335.93 V (833.98%)0.0 V5502.73 V (1375.68%)2600100.0 WDrop High
4 mm²32 A25 A2084.96 V (521.24%)0.0 V3439.2 V (859.8%)1625062.5 WDrop High
6 mm²41 A32 A1389.97 V (347.49%)0.0 V2292.8 V (573.2%)1083375.0 WDrop High
10 mm²57 A44 A833.98 V (208.5%)0.0 V1375.68 V (343.92%)650025.0 WDrop High
16 mm²76 A59 A521.24 V (130.31%)0.0 V859.8 V (214.95%)406265.6 WDrop High
25 mm²101 A78 A333.59 V (83.4%)66.4 V550.27 V (137.57%)260010.0 WDrop High
35 mm²125 A97 A238.28 V (59.57%)161.7 V393.05 V (98.26%)185721.4 WDrop High
50 mm²151 A118 A166.8 V (41.7%)233.2 V275.14 V (68.78%)130005.0 WDrop High
70 mm²192 A150 A119.14 V (29.79%)280.9 V196.53 V (49.13%)92860.7 WDrop High
95 mm²232 A181 A87.79 V (21.95%)312.2 V144.81 V (36.2%)68423.7 WDrop High
120 mm²269 A210 A69.5 V (17.37%)330.5 V114.64 V (28.66%)54168.7 WDrop High
150 mm²309 A241 A55.6 V (13.9%)344.4 V91.71 V (22.93%)43335.0 WDrop High
185 mm²353 A275 A45.08 V (11.27%)354.9 V74.36 V (18.59%)35136.5 WDrop High
240 mm²415 A324 A34.75 V (8.69%)365.3 V57.32 V (14.33%)27084.4 WDrop High
300 mm²477 A372 A27.8 V (6.95%)372.2 V45.86 V (11.46%)21667.5 WDrop High
400 mm²570 A445 A20.85 V (5.21%)379.2 V34.39 V (8.6%)16250.6 WDrop High

FAQ — 450 Amp Cable Size at 500 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 450A at 500 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 450A over 500m at 400V (voltage drop: 10.43V or 2.6%).

What is the power capacity of 450A at 400V?

At unity power factor, 450A at 400V supports 311.77 kW with a standard 450A circuit breaker.