450 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 5.78V (2.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 47.65V (20.72%)
Voltage at Load224.2 VLine Loss: 2600.1 W
Max Power & Breaker103.5 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7704.0 V (3349.57%)0.0 V12708.0 V (5525.22%)3466800.0 WDrop High
2.5 mm²24 A18 A4622.4 V (2009.74%)0.0 V7624.8 V (3315.13%)2080080.0 WDrop High
4 mm²32 A25 A2889.0 V (1256.09%)0.0 V4765.5 V (2071.96%)1300050.0 WDrop High
6 mm²41 A32 A1926.0 V (837.39%)0.0 V3177.0 V (1381.3%)866700.0 WDrop High
10 mm²57 A44 A1155.6 V (502.43%)0.0 V1906.2 V (828.78%)520020.0 WDrop High
16 mm²76 A59 A722.25 V (314.02%)0.0 V1191.38 V (517.99%)325012.5 WDrop High
25 mm²101 A78 A462.24 V (200.97%)0.0 V762.48 V (331.51%)208008.0 WDrop High
35 mm²125 A97 A330.17 V (143.55%)0.0 V544.63 V (236.8%)148577.1 WDrop High
50 mm²151 A118 A231.12 V (100.49%)0.0 V381.24 V (165.76%)104004.0 WDrop High
70 mm²192 A150 A165.09 V (71.78%)64.9 V272.31 V (118.4%)74288.6 WDrop High
95 mm²232 A181 A121.64 V (52.89%)108.4 V200.65 V (87.24%)54738.9 WDrop High
120 mm²269 A210 A96.3 V (41.87%)133.7 V158.85 V (69.07%)43335.0 WDrop High
150 mm²309 A241 A77.04 V (33.5%)153.0 V127.08 V (55.25%)34668.0 WDrop High
185 mm²353 A275 A62.46 V (27.16%)167.5 V103.04 V (44.8%)28109.2 WDrop High
240 mm²415 A324 A48.15 V (20.93%)181.8 V79.42 V (34.53%)21667.5 WDrop High
300 mm²477 A372 A38.52 V (16.75%)191.5 V63.54 V (27.63%)17334.0 WDrop High
400 mm²570 A445 A28.89 V (12.56%)201.1 V47.65 V (20.72%)13000.5 WDrop High

FAQ — 450 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 450A at 600 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 450A over 600m at 230V (voltage drop: 5.78V or 2.51%).

What is the power capacity of 450A at 230V?

At unity power factor, 450A at 230V supports 103.5 kW with a standard 450A circuit breaker.