475 Amp Cable Size at 120 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 7.04V (1.76%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.71V (2.18%)
Voltage at Load393.0 VLine Loss: 5794.1 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1408.5 V (352.13%)0.0 V2323.37 V (580.84%)1158810.0 WDrop High
2.5 mm²24 A18 A845.1 V (211.28%)0.0 V1394.02 V (348.51%)695286.0 WDrop High
4 mm²32 A25 A528.19 V (132.05%)0.0 V871.26 V (217.82%)434553.8 WDrop High
6 mm²41 A32 A352.13 V (88.03%)47.9 V580.84 V (145.21%)289702.5 WDrop High
10 mm²57 A44 A211.28 V (52.82%)188.7 V348.51 V (87.13%)173821.5 WDrop High
16 mm²76 A59 A132.05 V (33.01%)268.0 V217.82 V (54.45%)108638.4 WDrop High
25 mm²101 A78 A84.51 V (21.13%)315.5 V139.4 V (34.85%)69528.6 WDrop High
35 mm²125 A97 A60.36 V (15.09%)339.6 V99.57 V (24.89%)49663.3 WDrop High
50 mm²151 A118 A42.26 V (10.56%)357.7 V69.7 V (17.43%)34764.3 WDrop High
70 mm²192 A150 A30.18 V (7.55%)369.8 V49.79 V (12.45%)24831.6 WDrop High
95 mm²232 A181 A22.24 V (5.56%)377.8 V36.68 V (9.17%)18297.0 WDrop High
120 mm²269 A210 A17.61 V (4.4%)382.4 V29.04 V (7.26%)14485.1 WDrop High
150 mm²309 A241 A14.09 V (3.52%)385.9 V23.23 V (5.81%)11588.1 WDrop High
185 mm²353 A275 A11.42 V (2.86%)388.6 V18.84 V (4.71%)9395.8 WDrop High
240 mm²415 A324 A8.8 V (2.2%)391.2 V14.52 V (3.63%)7242.6 WDrop High
300 mm²477 A372 A7.04 V (1.76%)393.0 V11.62 V (2.9%)5794.1 W✓ OK (≤3%)
400 mm²570 A445 A5.28 V (1.32%)394.7 V8.71 V (2.18%)4345.5 W✓ OK (≤3%)

FAQ — 475 Amp Cable Size at 120 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 475A at 120 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 475A over 120m at 400V (voltage drop: 7.04V or 1.76%).

What is the power capacity of 475A at 400V?

At unity power factor, 475A at 400V supports 329.09 kW with a standard 500A circuit breaker.