475 Amp Cable Size at 200 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.08V (2.21%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.77V (7.29%)
Voltage at Load224.9 VLine Loss: 2414.2 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2710.67 V (1178.55%)0.0 V4471.33 V (1944.06%)1287566.7 WDrop High
2.5 mm²24 A18 A1626.4 V (707.13%)0.0 V2682.8 V (1166.43%)772540.0 WDrop High
4 mm²32 A25 A1016.5 V (441.96%)0.0 V1676.75 V (729.02%)482837.5 WDrop High
6 mm²41 A32 A677.67 V (294.64%)0.0 V1117.83 V (486.01%)321891.7 WDrop High
10 mm²57 A44 A406.6 V (176.78%)0.0 V670.7 V (291.61%)193135.0 WDrop High
16 mm²76 A59 A254.12 V (110.49%)0.0 V419.19 V (182.26%)120709.4 WDrop High
25 mm²101 A78 A162.64 V (70.71%)67.4 V268.28 V (116.64%)77254.0 WDrop High
35 mm²125 A97 A116.17 V (50.51%)113.8 V191.63 V (83.32%)55181.4 WDrop High
50 mm²151 A118 A81.32 V (35.36%)148.7 V134.14 V (58.32%)38627.0 WDrop High
70 mm²192 A150 A58.09 V (25.25%)171.9 V95.81 V (41.66%)27590.7 WDrop High
95 mm²232 A181 A42.8 V (18.61%)187.2 V70.6 V (30.7%)20330.0 WDrop High
120 mm²269 A210 A33.88 V (14.73%)196.1 V55.89 V (24.3%)16094.6 WDrop High
150 mm²309 A241 A27.11 V (11.79%)202.9 V44.71 V (19.44%)12875.7 WDrop High
185 mm²353 A275 A21.98 V (9.56%)208.0 V36.25 V (15.76%)10439.7 WDrop High
240 mm²415 A324 A16.94 V (7.37%)213.1 V27.95 V (12.15%)8047.3 WDrop High
300 mm²477 A372 A13.55 V (5.89%)216.4 V22.36 V (9.72%)6437.8 WDrop High
400 mm²570 A445 A10.16 V (4.42%)219.8 V16.77 V (7.29%)4828.4 W~ ≤5%

FAQ — 475 Amp Cable Size at 200 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 475A at 200 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 475A over 200m at 230V (voltage drop: 5.08V or 2.21%).

What is the power capacity of 475A at 230V?

At unity power factor, 475A at 230V supports 109.25 kW with a standard 500A circuit breaker.