32 Amp Cable Size at 200 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 5.48V (2.38%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.45V (2.81%)
Voltage at Load224.5 VLine Loss: 175.3 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A182.61 V (79.4%)47.4 V301.23 V (130.97%)5843.6 WDrop High
2.5 mm²24 A18 A109.57 V (47.64%)120.4 V180.74 V (78.58%)3506.2 WDrop High
4 mm²32 A25 A68.48 V (29.77%)161.5 V112.96 V (49.11%)2191.4 WDrop High
6 mm²41 A32 A45.65 V (19.85%)184.3 V75.31 V (32.74%)1460.9 WDrop High
10 mm²57 A44 A27.39 V (11.91%)202.6 V45.18 V (19.65%)876.5 WDrop High
16 mm²76 A59 A17.12 V (7.44%)212.9 V28.24 V (12.28%)547.8 WDrop High
25 mm²101 A78 A10.96 V (4.76%)219.0 V18.07 V (7.86%)350.6 W~ ≤5%
35 mm²125 A97 A7.83 V (3.4%)222.2 V12.91 V (5.61%)250.4 W~ ≤5%
50 mm²151 A118 A5.48 V (2.38%)224.5 V9.04 V (3.93%)175.3 W✓ OK (≤3%)
70 mm²192 A150 A3.91 V (1.7%)226.1 V6.45 V (2.81%)125.2 W✓ OK (≤3%)
95 mm²232 A181 A2.88 V (1.25%)227.1 V4.76 V (2.07%)92.3 W✓ OK (≤3%)
120 mm²269 A210 A2.28 V (0.99%)227.7 V3.77 V (1.64%)73.0 W✓ OK (≤3%)
150 mm²309 A241 A1.83 V (0.79%)228.2 V3.01 V (1.31%)58.4 W✓ OK (≤3%)
185 mm²353 A275 A1.48 V (0.64%)228.5 V2.44 V (1.06%)47.4 W✓ OK (≤3%)
240 mm²415 A324 A1.14 V (0.5%)228.9 V1.88 V (0.82%)36.5 W✓ OK (≤3%)
300 mm²477 A372 A0.91 V (0.4%)229.1 V1.51 V (0.65%)29.2 W✓ OK (≤3%)
400 mm²570 A445 A0.68 V (0.3%)229.3 V1.13 V (0.49%)21.9 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 200 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 32A at 200 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 32A over 200m at 230V (voltage drop: 5.48V or 2.38%).

What is the power capacity of 32A at 230V?

At unity power factor, 32A at 230V supports 7.36 kW with a standard 32A circuit breaker.