475 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.34V (0.71%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.42V (0.87%)
Voltage at Load47.7 VLine Loss: 160.9 W
Max Power & Breaker22.8 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A67.77 V (141.18%)0.0 V111.78 V (232.88%)32189.2 WDrop High
2.5 mm²24 A18 A40.66 V (84.71%)7.3 V67.07 V (139.73%)19313.5 WDrop High
4 mm²32 A25 A25.41 V (52.94%)22.6 V41.92 V (87.33%)12070.9 WDrop High
6 mm²41 A32 A16.94 V (35.3%)31.1 V27.95 V (58.22%)8047.3 WDrop High
10 mm²57 A44 A10.16 V (21.18%)37.8 V16.77 V (34.93%)4828.4 WDrop High
16 mm²76 A59 A6.35 V (13.24%)41.6 V10.48 V (21.83%)3017.7 WDrop High
25 mm²101 A78 A4.07 V (8.47%)43.9 V6.71 V (13.97%)1931.3 WDrop High
35 mm²125 A97 A2.9 V (6.05%)45.1 V4.79 V (9.98%)1379.5 WDrop High
50 mm²151 A118 A2.03 V (4.24%)46.0 V3.35 V (6.99%)965.7 WDrop High
70 mm²192 A150 A1.45 V (3.03%)46.5 V2.4 V (4.99%)689.8 WDrop High
95 mm²232 A181 A1.07 V (2.23%)46.9 V1.76 V (3.68%)508.2 WDrop High
120 mm²269 A210 A0.85 V (1.76%)47.2 V1.4 V (2.91%)402.4 WDrop High
150 mm²309 A241 A0.68 V (1.41%)47.3 V1.12 V (2.33%)321.9 WDrop High
185 mm²353 A275 A0.55 V (1.14%)47.5 V0.91 V (1.89%)261.0 WDrop High
240 mm²415 A324 A0.42 V (0.88%)47.6 V0.7 V (1.46%)201.2 WDrop High
300 mm²477 A372 A0.34 V (0.71%)47.7 V0.56 V (1.16%)160.9 W✓ OK (≤3%)
400 mm²570 A445 A0.25 V (0.53%)47.7 V0.42 V (0.87%)120.7 W✓ OK (≤3%)

FAQ — 475 Amp Cable Size at 5 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 475A at 5 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 475A over 5m at 48V (voltage drop: 0.34V or 0.71%).

What is the power capacity of 475A at 48V?

At unity power factor, 475A at 48V supports 22.8 kW with a standard 500A circuit breaker.