5 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 6.05V (2.63%)
Voltage at Load224.9 VLine Loss: 25.7 W
Max Power & Breaker1.15 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A85.6 V (37.22%)144.4 V141.2 V (61.39%)428.0 WDrop High
2.5 mm²24 A18 A51.36 V (22.33%)178.6 V84.72 V (36.83%)256.8 WDrop High
4 mm²32 A25 A32.1 V (13.96%)197.9 V52.95 V (23.02%)160.5 WDrop High
6 mm²41 A32 A21.4 V (9.3%)208.6 V35.3 V (15.35%)107.0 WDrop High
10 mm²57 A44 A12.84 V (5.58%)217.2 V21.18 V (9.21%)64.2 WDrop High
16 mm²76 A59 A8.03 V (3.49%)222.0 V13.24 V (5.76%)40.1 W~ ≤5%
25 mm²101 A78 A5.14 V (2.23%)224.9 V8.47 V (3.68%)25.7 W✓ OK (≤3%)
35 mm²125 A97 A3.67 V (1.6%)226.3 V6.05 V (2.63%)18.3 W✓ OK (≤3%)
50 mm²151 A118 A2.57 V (1.12%)227.4 V4.24 V (1.84%)12.8 W✓ OK (≤3%)
70 mm²192 A150 A1.83 V (0.8%)228.2 V3.03 V (1.32%)9.2 W✓ OK (≤3%)
95 mm²232 A181 A1.35 V (0.59%)228.6 V2.23 V (0.97%)6.8 W✓ OK (≤3%)
120 mm²269 A210 A1.07 V (0.47%)228.9 V1.76 V (0.77%)5.3 W✓ OK (≤3%)
150 mm²309 A241 A0.86 V (0.37%)229.1 V1.41 V (0.61%)4.3 W✓ OK (≤3%)
185 mm²353 A275 A0.69 V (0.3%)229.3 V1.14 V (0.5%)3.5 W✓ OK (≤3%)
240 mm²415 A324 A0.54 V (0.23%)229.5 V0.88 V (0.38%)2.7 W✓ OK (≤3%)
300 mm²477 A372 A0.43 V (0.19%)229.6 V0.71 V (0.31%)2.1 W✓ OK (≤3%)
400 mm²570 A445 A0.32 V (0.14%)229.7 V0.53 V (0.23%)1.6 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 600 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 5A at 600 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 5A over 600m at 230V (voltage drop: 5.14V or 2.23%).

What is the power capacity of 5A at 230V?

At unity power factor, 5A at 230V supports 1.15 kW with a standard 6A circuit breaker.