5 Amp Cable Size at 90 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 4.81V (2.09%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 5.29V (2.3%)
Voltage at Load225.2 VLine Loss: 24.1 W
Max Power & Breaker1.15 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.84 V (5.58%)217.2 V21.18 V (9.21%)64.2 WDrop High
2.5 mm²24 A18 A7.7 V (3.35%)222.3 V12.71 V (5.53%)38.5 W~ ≤5%
4 mm²32 A25 A4.81 V (2.09%)225.2 V7.94 V (3.45%)24.1 W✓ OK (≤3%)
6 mm²41 A32 A3.21 V (1.4%)226.8 V5.29 V (2.3%)16.1 W✓ OK (≤3%)
10 mm²57 A44 A1.93 V (0.84%)228.1 V3.18 V (1.38%)9.6 W✓ OK (≤3%)
16 mm²76 A59 A1.2 V (0.52%)228.8 V1.99 V (0.86%)6.0 W✓ OK (≤3%)
25 mm²101 A78 A0.77 V (0.33%)229.2 V1.27 V (0.55%)3.9 W✓ OK (≤3%)
35 mm²125 A97 A0.55 V (0.24%)229.4 V0.91 V (0.39%)2.8 W✓ OK (≤3%)
50 mm²151 A118 A0.39 V (0.17%)229.6 V0.64 V (0.28%)1.9 W✓ OK (≤3%)
70 mm²192 A150 A0.28 V (0.12%)229.7 V0.45 V (0.2%)1.4 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.09%)229.8 V0.33 V (0.15%)1.0 W✓ OK (≤3%)
120 mm²269 A210 A0.16 V (0.07%)229.8 V0.26 V (0.12%)0.8 W✓ OK (≤3%)
150 mm²309 A241 A0.13 V (0.06%)229.9 V0.21 V (0.09%)0.6 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.05%)229.9 V0.17 V (0.07%)0.5 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.03%)229.9 V0.13 V (0.06%)0.4 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.03%)229.9 V0.11 V (0.05%)0.3 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.02%)230.0 V0.08 V (0.03%)0.2 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 90 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 5A at 90 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 5A over 90m at 230V (voltage drop: 4.81V or 2.09%).

What is the power capacity of 5A at 230V?

At unity power factor, 5A at 230V supports 1.15 kW with a standard 6A circuit breaker.