16 Amp Cable Size at 90 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 6.16V (2.68%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 6.35V (2.76%)
Voltage at Load223.8 VLine Loss: 98.6 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A41.09 V (17.86%)188.9 V67.78 V (29.47%)657.4 WDrop High
2.5 mm²24 A18 A24.65 V (10.72%)205.3 V40.67 V (17.68%)394.4 WDrop High
4 mm²32 A25 A15.41 V (6.7%)214.6 V25.42 V (11.05%)246.5 WDrop High
6 mm²41 A32 A10.27 V (4.47%)219.7 V16.94 V (7.37%)164.4 W~ ≤5%
10 mm²57 A44 A6.16 V (2.68%)223.8 V10.17 V (4.42%)98.6 W✓ OK (≤3%)
16 mm²76 A59 A3.85 V (1.67%)226.1 V6.35 V (2.76%)61.6 W✓ OK (≤3%)
25 mm²101 A78 A2.47 V (1.07%)227.5 V4.07 V (1.77%)39.4 W✓ OK (≤3%)
35 mm²125 A97 A1.76 V (0.77%)228.2 V2.9 V (1.26%)28.2 W✓ OK (≤3%)
50 mm²151 A118 A1.23 V (0.54%)228.8 V2.03 V (0.88%)19.7 W✓ OK (≤3%)
70 mm²192 A150 A0.88 V (0.38%)229.1 V1.45 V (0.63%)14.1 W✓ OK (≤3%)
95 mm²232 A181 A0.65 V (0.28%)229.4 V1.07 V (0.47%)10.4 W✓ OK (≤3%)
120 mm²269 A210 A0.51 V (0.22%)229.5 V0.85 V (0.37%)8.2 W✓ OK (≤3%)
150 mm²309 A241 A0.41 V (0.18%)229.6 V0.68 V (0.29%)6.6 W✓ OK (≤3%)
185 mm²353 A275 A0.33 V (0.14%)229.7 V0.55 V (0.24%)5.3 W✓ OK (≤3%)
240 mm²415 A324 A0.26 V (0.11%)229.7 V0.42 V (0.18%)4.1 W✓ OK (≤3%)
300 mm²477 A372 A0.21 V (0.09%)229.8 V0.34 V (0.15%)3.3 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.07%)229.8 V0.25 V (0.11%)2.5 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 90 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 16A at 90 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 16A over 90m at 230V (voltage drop: 6.16V or 2.68%).

What is the power capacity of 16A at 230V?

At unity power factor, 16A at 230V supports 3.68 kW with a standard 16A circuit breaker.