50 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 50 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 9.75V (2.35%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 10.19V (2.46%)
Voltage at Load405.2 VLine Loss: 844.7 W
Max Power & Breaker35.94 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A617.76 V (148.86%)0.0 V1019.02 V (245.55%)53500.0 WDrop High
2.5 mm²24 A18 A370.66 V (89.32%)44.3 V611.41 V (147.33%)32100.0 WDrop High
4 mm²32 A25 A231.66 V (55.82%)183.3 V382.13 V (92.08%)20062.5 WDrop High
6 mm²41 A32 A154.44 V (37.21%)260.6 V254.76 V (61.39%)13375.0 WDrop High
10 mm²57 A44 A92.66 V (22.33%)322.3 V152.85 V (36.83%)8025.0 WDrop High
16 mm²76 A59 A57.92 V (13.96%)357.1 V95.53 V (23.02%)5015.6 WDrop High
25 mm²101 A78 A37.07 V (8.93%)377.9 V61.14 V (14.73%)3210.0 WDrop High
35 mm²125 A97 A26.48 V (6.38%)388.5 V43.67 V (10.52%)2292.9 WDrop High
50 mm²151 A118 A18.53 V (4.47%)396.5 V30.57 V (7.37%)1605.0 W~ ≤5%
70 mm²192 A150 A13.24 V (3.19%)401.8 V21.84 V (5.26%)1146.4 W~ ≤5%
95 mm²232 A181 A9.75 V (2.35%)405.2 V16.09 V (3.88%)844.7 W✓ OK (≤3%)
120 mm²269 A210 A7.72 V (1.86%)407.3 V12.74 V (3.07%)668.7 W✓ OK (≤3%)
150 mm²309 A241 A6.18 V (1.49%)408.8 V10.19 V (2.46%)535.0 W✓ OK (≤3%)
185 mm²353 A275 A5.01 V (1.21%)410.0 V8.26 V (1.99%)433.8 W✓ OK (≤3%)
240 mm²415 A324 A3.86 V (0.93%)411.1 V6.37 V (1.53%)334.4 W✓ OK (≤3%)
300 mm²477 A372 A3.09 V (0.74%)411.9 V5.1 V (1.23%)267.5 W✓ OK (≤3%)
400 mm²570 A445 A2.32 V (0.56%)412.7 V3.82 V (0.92%)200.6 W✓ OK (≤3%)

FAQ — 50 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 50A at 500 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 50A over 500m at 415V (voltage drop: 9.75V or 2.35%).

What is the power capacity of 50A at 415V?

At unity power factor, 50A at 415V supports 35.94 kW with a standard 50A circuit breaker.