50 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 50 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.55V (2.3%)
Voltage at Load405.7 VLine Loss: 802.5 W
Max Power & Breaker35.94 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A61.78 V (14.89%)353.2 V101.9 V (24.55%)5350.0 WDrop High
2.5 mm²24 A18 A37.07 V (8.93%)377.9 V61.14 V (14.73%)3210.0 WDrop High
4 mm²32 A25 A23.17 V (5.58%)391.8 V38.21 V (9.21%)2006.2 WDrop High
6 mm²41 A32 A15.44 V (3.72%)399.6 V25.48 V (6.14%)1337.5 WDrop High
10 mm²57 A44 A9.27 V (2.23%)405.7 V15.29 V (3.68%)802.5 W✓ OK (≤3%)
16 mm²76 A59 A5.79 V (1.4%)409.2 V9.55 V (2.3%)501.6 W✓ OK (≤3%)
25 mm²101 A78 A3.71 V (0.89%)411.3 V6.11 V (1.47%)321.0 W✓ OK (≤3%)
35 mm²125 A97 A2.65 V (0.64%)412.4 V4.37 V (1.05%)229.3 W✓ OK (≤3%)
50 mm²151 A118 A1.85 V (0.45%)413.1 V3.06 V (0.74%)160.5 W✓ OK (≤3%)
70 mm²192 A150 A1.32 V (0.32%)413.7 V2.18 V (0.53%)114.6 W✓ OK (≤3%)
95 mm²232 A181 A0.98 V (0.24%)414.0 V1.61 V (0.39%)84.5 W✓ OK (≤3%)
120 mm²269 A210 A0.77 V (0.19%)414.2 V1.27 V (0.31%)66.9 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.15%)414.4 V1.02 V (0.25%)53.5 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.12%)414.5 V0.83 V (0.2%)43.4 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.09%)414.6 V0.64 V (0.15%)33.4 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.07%)414.7 V0.51 V (0.12%)26.7 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.06%)414.8 V0.38 V (0.09%)20.1 W✓ OK (≤3%)

FAQ — 50 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 50A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 50A over 50m at 415V (voltage drop: 9.27V or 2.23%).

What is the power capacity of 50A at 415V?

At unity power factor, 50A at 415V supports 35.94 kW with a standard 50A circuit breaker.