500 Amp Cable Size at 15 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 0.8V (0.35%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.32V (0.58%)
Voltage at Load229.2 VLine Loss: 401.2 W
Max Power & Breaker115.0 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A214.0 V (93.04%)16.0 V353.0 V (153.48%)107000.0 WDrop High
2.5 mm²24 A18 A128.4 V (55.83%)101.6 V211.8 V (92.09%)64200.0 WDrop High
4 mm²32 A25 A80.25 V (34.89%)149.8 V132.38 V (57.55%)40125.0 WDrop High
6 mm²41 A32 A53.5 V (23.26%)176.5 V88.25 V (38.37%)26750.0 WDrop High
10 mm²57 A44 A32.1 V (13.96%)197.9 V52.95 V (23.02%)16050.0 WDrop High
16 mm²76 A59 A20.06 V (8.72%)209.9 V33.09 V (14.39%)10031.2 WDrop High
25 mm²101 A78 A12.84 V (5.58%)217.2 V21.18 V (9.21%)6420.0 WDrop High
35 mm²125 A97 A9.17 V (3.99%)220.8 V15.13 V (6.58%)4585.7 WDrop High
50 mm²151 A118 A6.42 V (2.79%)223.6 V10.59 V (4.6%)3210.0 WDrop High
70 mm²192 A150 A4.59 V (1.99%)225.4 V7.56 V (3.29%)2292.9 WDrop High
95 mm²232 A181 A3.38 V (1.47%)226.6 V5.57 V (2.42%)1689.5 WDrop High
120 mm²269 A210 A2.67 V (1.16%)227.3 V4.41 V (1.92%)1337.5 WDrop High
150 mm²309 A241 A2.14 V (0.93%)227.9 V3.53 V (1.53%)1070.0 WDrop High
185 mm²353 A275 A1.74 V (0.75%)228.3 V2.86 V (1.24%)867.6 WDrop High
240 mm²415 A324 A1.34 V (0.58%)228.7 V2.21 V (0.96%)668.8 WDrop High
300 mm²477 A372 A1.07 V (0.47%)228.9 V1.76 V (0.77%)535.0 WDrop High
400 mm²570 A445 A0.8 V (0.35%)229.2 V1.32 V (0.58%)401.2 W✓ OK (≤3%)

FAQ — 500 Amp Cable Size at 15 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 500A at 15 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 500A over 15m at 230V (voltage drop: 0.8V or 0.35%).

What is the power capacity of 500A at 230V?

At unity power factor, 500A at 230V supports 115.0 kW with a standard 500A circuit breaker.